Use this page to configure the main operating parameters for GateKeeper before the system is taken into service.
Configure the core behavior for the installed unit.
Select the program used to control the gate, boom, carousel, or door.
| Index | Range | Format | Factory setting | Example | |
| GKEPRG | 1..2 | 0..5 |
0 = Deactivated 1 = Gate without end-stop sensors 2 = Gate with end-stop sensors 3 = Carousel 4 = Boom 5 = Door |
0 |
GKEPRG 1 |
Select the normal access-control mode used by GateKeeper when no planned schedule change is active.
| Index | Range | Format | Factory setting | Example | |
| GKEACC | 1..2 | 0..6 |
0 = Permanently closed 4 = Calendar-based access control 5 = Closed but everyone can open 6 = Closed but everyone can open with road sensor |
2 |
GKEACC 0 |
GateKeeper can store a custom unit name and a custom greeting text.
Store a custom GateKeeper name text.
| Index | Range | Format | Factory setting | Example | |
| GKENAVN | - | Stored text value | Text string | Blank | GKENAVN Main Gate |
Store a custom GateKeeper greeting text.
| Index | Range | Format | Factory setting | Example | |
| GKEHILS | - | Stored text value | Text string | Blank | GKEHILS Welcome |
Use these parameters for a one-time planned change of the GateKeeper access state. Both the start time and the stop time must be configured. At the start time, GateKeeper applies the configured start state. At the stop time, GateKeeper applies the configured stop state and clears the scheduled switching values.
Select the direct access-control state that GateKeeper must apply at the planned start time.
| Index | Range | Format | Factory setting | Example | |
| GKEACCSTART | 1..2 | 0,1,2,3,5 |
0 = Permanently closed |
0 |
GKEACCSTART 2 |
Set the exact planned start time for the scheduled change. Scheduled switching stays inactive until both the start time and the stop time are set.
| Index | Range | Format | Factory setting | Example | |
| GKEACCSTARTTIME | 1..2 | 0..2147483647 | Planned start timestamp for scheduled switching |
0 |
GKEACCSTARTTIME 1714978800 |
Select the direct access-control state that GateKeeper must apply when the stop time is reached.
| Index | Range | Format | Factory setting | Example | |
| GKEACCSTOP | 1..2 | 0,1,2,3,5 |
0 = Permanently closed |
0 |
GKEACCSTOP 0 |
Set when GateKeeper must end the planned state and switch to the configured stop state.
| Index | Range | Format | Factory setting | Example | |
| GKEACCSTOPTIME | 1..2 | 0..2147483647 | Planned stop timestamp for scheduled switching |
0 |
GKEACCSTOPTIME 1714982400 |
Enable the road-sensor inputs used by the road-sensor-based access modes.
Enable the inside road-sensor input for the selected GateKeeper slot.
Enable the outside road-sensor input for the selected GateKeeper slot.
| Index | Range | Format | Factory setting | Example | |
| GKERSOUT | 1..2 | 0..1 |
0 = Disabled |
0 |
GKERSOUT 1 |
Set how long GateKeeper waits before it closes again after an approved opening cycle.