Specifications for the OnSiteLight MBO cabinet series.
| Description | OSL 0000-12-1 /D MBO | OSL 6000-8-2 /D MBO | OSL 4000-5-1 /D MBO | OSL 4000-5-2 /D MBO |
| Item number | 1004727 |
1004471 |
1004544 |
|
| Series | MBO |
MBO |
MBO |
MBO |
| Model | Cabinet |
Cabinet |
Cabinet |
Cabinet |
| Type | Stand-alone |
Stand-alone |
Stand-alone |
Stand-alone |
| Installation | Outdoor/indoor use |
Outdoor/indoor use |
Outdoor/indoor use |
Outdoor/indoor use |
| Upstream DO2 fuse, max. A | 63 |
63 |
63 |
63 |
| Full-load current A | 2 |
10 |
8 |
8 |
| Rated current InA | 63 |
63 |
63 |
63 |
| Diversity factor | 1,0 |
1,0 |
1,0 |
1,0 |
| Short-circuit current max. Icf kA | 16 |
16 |
16 |
16 |
| Earthing system - standard TN-C-S, alternatively TN-S or TT | TN-C-S |
TN-C-S |
TN-C-S |
TN-C-S |
| Frequency | 50 Hz |
50 Hz |
50 Hz |
50 Hz |
| Connection of supply cable in fuse element | - |
- |
- |
- |
| Connection of supply cable with cable lugs on copper bars | - |
- |
- |
- |
| Connection of supply cable in terminals | AL/CU 1,5-50 mm² |
AL/CU 16-95 mm² |
AL/CU 16-95 mm² |
|
| Loop-through option/parallel feed | yes |
yes |
yes |
yes |
| Max. cross-section for supply cable/loop-through cable | - |
2 // 4x50 AL and 2 // 1x50 AL (PE) |
2 // 4x95 AL and 2 // 1x95 AL (PE) |
2 // 4x95 AL and 2 // 1x95 AL (PE) |
| Max. supply-cable/loop-through cable diameter in mm | - |
42 |
42 |
42 |
| Ingress protection class IP | 54 |
54 |
54 |
54 |
| Extra metered 230 V/10 A output for other use | - |
- |
- |
yes |
| GSM controller/data logger/control | yes |
yes |
yes |
yes |
| Transient protection Type 2 | yes |
yes |
yes |
yes |
| Energy meter | yes |
yes |
yes |
yes |
| DALI communication | yes |
yes |
yes |
yes |
| Modbus communication | yes |
yes |
yes |
yes |
| Miniature circuit breaker 10 A 3P+N D characteristic | 1 |
- |
1 |
1 |
| Miniature circuit breaker 16 A 3P+N D characteristic | - |
1 |
- |
- |
| HPFI 40A/30mA | 1 |
1 |
1 |
1 |
| Suitable for maritime use | yes |
yes |
yes |
yes |
| Built according to standard DS/EN 61439-2 | yes |
yes |
yes |
yes |
Ambient temperature for indoor installation |
-5-25°C |
-5-25°C |
-5-25°C |
-5-25°C |
Ambient temperature for outdoor installation |
-25-30°C |
-25-30°C |
-25-30°C |
-25-30°C |
| Monitoring of protection devices (RCD/MCB) | yes |
yes |
yes |
yes |
| Monitoring of transient protection | yes |
yes |
yes |
yes |
| Monitoring of serial/DALI communication | yes |
yes |
yes |
yes |
| Monitoring of power supply | yes |
yes |
yes |
yes |
| LED lamps - max. total power | - |
6000 W |
4000 W |
4000 W |
DALI - communication with lamps |
yes |
yes |
yes |
yes |
| DALI - Max number of lamps | 12 |
8 |
5 |
5 |
| DALI - Max number of light sources per lamp | 4 |
4 |
4 |
4 |
| DALI - Max number of addresses | 48 |
32 |
20 |
20 |
| DALI - Max cable length with 1,5 mm2 | 300 metres |
300 metres |
300 metres |
300 metres |
| Thermostat-controlled heater 1x160W | - * |
- * |
- * |
- * |
| Buttons with LED light for operation | Option |
Option |
4 |
4 |
| Button with LED light for operation of lamp 5 | - |
- |
- * |
- * |
| aKey - Tag reader for operation | Option |
Option |
yes |
yes |
| aKey - Max cable length | 300 metres |
300 metres |
300 metres |
300 metres |
| Cable glands for power cables included | no |
no |
no |
no |
| Lifting eyes | - |
- |
- |
- |
| Material | APO enclosures |
APO enclosures |
APO enclosures |
APO enclosures |
| Weight | 25 kg |
25 kg |
||
| External dimensions (H x W x D) |
|
1207x302x180 mm |
1207x302x180 mm |
* Option
Public revision 21/08/2026