Settings for the LoadSharing application.
Set whether the application is enabled or disabled.
Parameter |
Index | Range | Format | Factory setting | Example |
| LOSON | - | 0..1 | 0 = Disabled 1 = Enabled |
0 | LOSON 1 |
Set the virtual rated current of the electrical cabinet. For example, the electrical cabinet can have a rated current of 800A, while only 600A is available on site. If the maximum allowed rated current is exceeded for the configured time, outlets are switched off until the power consumption is below 600A again.
Parameter |
Index | Range | Format | Factory setting | Example |
| LOSMAXAC | - |
0..9999 | Ampere | 0 | LOSMAXAC 800 |
Set the maximum allowed time that the electrical cabinet power consumption can be exceeded. For example, the maximum allowed power consumption can be exceeded for 1000 ms. If the maximum allowed rated current is exceeded for the configured time, outlets are switched off until the power consumption is below, for example, 600A again.
Parameter |
Index | Range | Format | Factory setting | Example |
| LOSMAXTC | - | 0..10000 | Milliseconds |
1000 | LOSMAXTC 1500 |
Set the maximum allowed power consumption per outlet. For example, a 63A CEE outlet can be limited to 50A. If the maximum allowed power consumption is exceeded for the configured time, the outlet is switched off.
Parameter |
Index | Range | Format | Factory setting | Example |
| LOSMAXAO# | 1..12 | 0..400 | Ampere | 0 | LOSMAXAO1 16 |
Set the maximum allowed time per outlet that power consumption can be exceeded. For example, the maximum allowed power consumption for outlet 1 can be exceeded for 1000 ms. If the maximum allowed power consumption is exceeded for the configured time, the outlet is switched off.
Parameter |
Index | Range | Format | Factory setting | Example |
| LOSMAXTO# | 1..12 | 0..10000 | Milliseconds |
1000 | LOSMAXTO1 1500 |
Public revision 21/08/2026