| LampA physical lamp unit that can contain one or more light sources. |
Fault cause |
Remedy |
|
Off
|
The supply voltage is disconnected.
Fault causes:
- Fuse has blown.
- Supply voltage disconnected.
or
The switch is on and the electrical outlet is paused.
Fault causes:
- The outlet was not switched on by the user within the configured period.
- Electrical consumption was not registered within the configured period.
|
- Check that any section switch in the cabinet is switched on.
- Check that any protective equipment in the cabinet is switched on.
- Check that 400V can be measured between the three phases in the cabinet incoming field.
- Check that 230V can be measured between each phase and neutral in the cabinet incoming field.
- Check that 24VDC can be measured on the VikMoteController with built-in GSM and data logger. unit in the cabinet.
or
- Switch off the outlet switch.
- Check that protective equipment (RCD, circuit breaker, or combination breaker) is switched on.
- Switch on the outlet switch.
- Start the outlet with normal local access, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media.. If the same outlet is deliberately selected in Emiko/App/Web, the equipment can try again while the plug is still inserted, provided normal electrical safety checks pass.
- If the outlet remains paused for local access, remove and reinsert the plug. No plug means no power.
- The outlet switches on.
|
|
1 flash followed by pause
|
Protective equipment in the cabinet for the outlet has tripped. Protective equipment must be switched on before the outlet can be used.
Fault causes:
- Tripped because of a fault in the connected plug or cable.
- Tripped because of excessive power consumption.
- Tripped because of excessive leakage current.
- Tripped because of missing earth connection or bonding.
|
- Switch off the outlet switch.
- Check that protective equipment (RCD, circuit breaker, or combination breaker) is switched on.
- Check that the auxiliary contact on the protective equipment gives a signal when it is switched on.
- Check that the signal from the auxiliary contact is registered on the VikMoteController with built-in GSM and data logger. unit or on one of the expansion modules.
- Insert a plug into the outlet.
- Switch on the outlet switch.
- Switch on the outlet, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media..
- The outlet switches on.
- Wait 120 seconds and switch off the outlet.
- The outlet has been tested and works correctly.
|
|
2 flashes followed by pause
|
The contactor in the cabinet has been manually forced on, for example with a screwdriver. Note that energy consumption is not registered.
Fault cause:
- A screwdriver was used to force the contactor on.
- Vandalism or similar.
Remedy:
- Perform a visual inspection on site.
|
- Switch off the outlet switch for 5 seconds.
- Remove any screwdriver from the contactor.
- Check that no components are damaged.
- Insert a plug into the outlet.
- Switch on the outlet switch.
- Switch on the outlet, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media..
- The outlet switches on.
- Insert a plug and create energy consumption, for example by connecting a heater fan.
- Wait until consumption is registered on the energy-meter display.
- Wait 120 seconds and switch off the outlet.
- The outlet has been tested and works correctly.
|
|
3 flashes followed by pause
|
No feedback from the contactor that switches power to the outlet.
Fault causes:
- Defective contactor or auxiliary contact.
- Loose connection from auxiliary contact to VikMoteController with built-in GSM and data logger./expansion module.
Observation:
- When switching on the outlet is attempted, the contactor pulls in briefly.
Remedy:
- Check the status signal from the contactor.
|
- Switch off the outlet switch for 5 seconds.
- Insert a plug into the outlet.
- Switch on the outlet switch.
- Check that the contactor switches on, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media..
- Check that the auxiliary contact on the contactor gives a signal when the contactor switches on.
- Check that the signal from the auxiliary contact is registered on the VikMoteController with built-in GSM and data logger. unit or on one of the expansion modules.
- Switch off the outlet switch for 5 seconds.
- Switch on the outlet switch.
- Switch on the outlet, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media..
- The outlet switches on.
- Wait 120 seconds and switch off the outlet.
- The outlet has been tested and works correctly.
|
|
4 flashes followed by pause
|
Fault on the energy meter for the outlet. The system cannot communicate with the energy meter.
Fault causes:
- Defective energy meter.
- Loose connection on serial ModbusModbus is a serial communication protocol used with devices such as water meters and energy meters. communication between VikMoteController with built-in GSM and data logger. and energy meter.
Remedy:
- Replace the energy meter.
|
- Check that the energy meter is switched on and that the display is lit.
- Check the communication cable for loose connections.
- Check that termination is correct on the communication cable.
- Check that the energy meter has the correct address.
- Switch off the outlet switch for 5 seconds.
- Insert a plug into the outlet.
- Switch on the outlet switch.
- Switch on the outlet, for example by calling or using aKeyaKey is a key fob reader for RFID cards, tags, and similar access media..
- The outlet switches on.
- Wait 120 seconds and switch off the outlet.
- The outlet has been tested and works correctly.
|