LX4 PRO

Controller Mounting Supply voltage Digital inputs Digital outputs Analogue inputs Analogue inputs

Model: LX4 PRO

DIN rail mounting 8-36 VDC 8 8 4 2

SIM card

Insert a SIM card in the device if it was not supplied from the factory with a SIM card installed:

Power Supply

Supply voltage Terminal Use Note
8-36 VDC

28 - SUPP

29 - SUPP

Plus

24 VDC must be used

27 - PGND Minus

Digital inputs

Digital inputs Terminal Use Note
Ground 1 40 - SGND Ground for inputs 1..4 Must always be connected
Input 1 41 - DI1 Pulse signal from energy meter to electricity outlet 1 (alternative RS485)

Inputs are factory-set to S0IEC 62053-31 Class A S0 standard for pulse signals./NPNNPN is a negative signal (minus).

- Jumper 1+2+3+4 must be in position S

 

Signal must be between SGND and DIx

 

Read more about counter setup here

Input 2 42 - DI2 Pulse signal from energy meter to electricity outlet 2 (alternative RS485)
Input 3 43 - DI3 Pulse signal from energy meter to electricity outlet 3 (alternative RS485)
Input 4 44 - DI4 Pulse signal from energy meter to electricity outlet 4 (alternative RS485)
Input 5 45 - DI5 -

Use only PNPPNP is a positive signal (plus). signal

Signal on DIx must be 8-40 VDC

Input 6 46 - DI6 -
Input 7 47 - DI7 -
Input 8 48 - DI8 -
Ground 2 49 - SGND Ground for inputs 5..8 Must always be connected

Digital outputs

Digital outputs Terminal Use Note
Supply voltage 8-36 VDC 30 - DOUT SUPP + Supply voltage til udgange

Terminal 30 kan forbindes til klemme 29
Terminal 39 kan forbindes til klemme 27

39 - DOUT GND -
Output 1 31 - DO1 Output to contactor for electricity outlet 1, NONormally open.

Max. load is 1.5 A per output

Max. inductance for switching is 20 mH per output

 

Factory-set as an on/off output with the command DWTYPE. Use an interposing relay if the main contactor is 230 V

Output 2 32 - DO2 Output to contactor for electricity outlet 2, NONormally open.
Output 3 33 - DO3 Output to contactor for electricity outlet 3, NONormally open.
Output 4 34 - DO4 Output to contactor for electricity outlet 4, NONormally open.
Output 5 35 - DO5 -
Output 6 36 - DO6 -
Output 7 37 - DO7 -
Output 8 38 - DO8 -

RS485 port 1

RS485 communication as an alternative to pulse signal.

RS485 communication Terminal Use Note
Port 1

9 - RSA 1 (+)

RS485 non-inverting signal (A)

Jumper TERM1 is factory-fitted and a 120 ohm resistor terminates the bus

Read more about termination here

10 - RSB 1 (-)

RS485 inverting signal (B)

Ground 8 - SGND Ground for RS485

 

 