Configure parameters for WaterStation. Parameters must be configured before the system can be put into use.
Basic settings for the equipment.
Load factory settings. All parameters are set to the specified factory settings.
Note that the equipment restarts.
The following global parameter is adjusted automatically:
| Index | Range | Format | Factory Setting |
Example |
|
| WASFAC | - |
- |
- | - | WASFAC |
Configure which program the equipment must use.
| Parameter | Index | Range | Format | Factory Setting |
Example |
| WASPRG | - | 0..2 |
0 = Disabled 1 = WaterStation 2 = WaterStation G2 with bus system |
0 | WASPRG 1 |
Configure how the customer must be validated or whether the equipment is available for free use.
| Parameter | Index | Range | Format | Factory Setting | Example |
| - | 0..3 |
0 = Blocked (the equipment is blocked and cannot be used) 1 = Free (the equipment is open to all users for free use, and all consumption is registered to the system account) 2 = Payment (the equipment validates the customer, and only approved customers are accepted) 3 = Mixed (the equipment first uses Payment, and if the customer is not validated, Free is used) |
2 | WASACC 1 |
Configure the equipment name. The name is used, for example, if the equipment sends a message.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASNAME | - | Max. 20 characters | Numbers or letters | - | WASNAME Viking |
Configure the equipment greeting. The greeting is used, for example, if the equipment sends a message.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASREGARDS | - | Max. 20 characters | Numbers or letters | - | WASREGARDS Vikingegaarden |
Configure modules for the equipment. Note that modules are options, and the equipment can be delivered with or without modules.
Configure whether the equipment has a built-in energy meter for registering internal electricity consumption.
| Parameter | Index | Range | Format | Factory Setting |
Example |
| WASEGI | - | 0..1 |
0 = None 1 = Built-in |
0 | WASEGI 1 |
Configure whether the equipment must control and monitor heating to protect water pipes against frost.
| Parameter | Index | Range | Format | Factory Setting |
Example |
| WASHEAT | - | 0..1 |
0 = None 1 = Heating Control |
0 | WASHEAT 1 |
Configure parameters for water outlets.
Configure the number of water outlets the equipment is built with. For example, the equipment can be built with 2 water outlets.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASOUTLET | - | 0..3 |
0 = No outlets 1 = 1 outlet 2 = 2 outlets 3 = 3 outlets |
0 | WASOUTLET 1 |
Configure the time from when operation is started until the water outlet must be open. If the time expires, the user normally starts again, or another user can use the water outlet.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASSTARTTIM | - | 1..20 | Minutes | 8 | WASSTARTTIM 10 |
Configure the time from the last registered water consumption until the water outlet closes automatically. For example, if a water outlet is opened and no water consumption is registered during the specified period, the water outlet closes automatically.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASUSAGETIM | - | 0..32000 |
0 = Function disabled >0 = Number of minutes (recommended) |
1440 (one day) | WASUSAGETIM 2880 |
Configure parameters for the valve.
Configure which valve type is installed.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASVALTYPE# | 1..3 | 0..3 |
0 = None 1 = Solenoid valve (On/Off) 2 = Solenoid valve (Pulse) TBD 3 = Motor valve BFA 820 |
0 | WASVALTYPE 1 |
Configure parameters for the water meter.
Configure the water meter ratio. For example, 1 pulse corresponds to 10 litres of water.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASSCALE# | 1..3 | 0..1000 | Number of litres of water per pulse | 0 | WASSCALE1 10 |
Configure parameters for using a requisition number. With this function, the user can enter a requisition number, which is registered together with the water consumption. When the user calls the equipment, for example, an SMS is sent to the user. The user must reply with the required requisition number. When the equipment receives an SMS with the requisition number, the water opens.
Configure the time from when the user receives an SMS until the user must reply with a requisition number. If the user does not reply before the time expires, the user must call again, for example, and a new SMS is sent.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASORDTIM | - | 1..8 | Minutes | 2 | WASORDTIM 3 |
Configure parameters for how the lighting must work.
Configure the operating mode. Lighting can be controlled manually or set to automatic mode. In automatic mode, the light switches on shortly before sunset and switches off shortly after sunrise.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASLIGHT | - | 0..2 | 0 = Permanently off 1 = Permanently on 2 = Automatic (recommended) | 2 | WASLIGHT 1 |
Select output.
| Parameter | Index | Range | Format | Factory Setting | Example |
| WASLIGOUT | - | 0..1 |
0 = None 1 = Automatic (recommended) |
0 | - |
Status fields for reading values from the equipment.
Show equipment license status.
Public revision 21/08/2026