WeatherStation LX9 eco IO list

Use this page as the terminal and jumper reference for WeatherStation LX9 eco. The built-in controller is VikMote LX9 eco.

Hardware overview

Controller Mounting Supply voltage
VikMote LX9 eco Wall mounting, IP65 enclosure 100-260 VAC or 8-36 VDC

Interface overview

Interface Terminals Use Continue
Analog inputs AI1-AI2 and AGND 4-20 mA or 0-10 V weather and climate transmitters. Analog weather inputs
Digital inputs DI1-DI4 with GND, DI5 with DCOUT Pulse/contact instruments when the delivered setup supports the value. Digital and counter inputs
RS485 485_1_A/485_1_B/485_SGND and 485_2_A/485_2_B/485_SGND Supported serial/driver weather, climate, and level instruments. RS485 weather sensors
1-Wire 1Wire and SGND Simple temperature measurement where required by the installation. 1-Wire inputs

Supply voltage

Supply Terminal Use Note
100-260 VAC N Neutral VAC and VDC supply can be connected at the same time.
P Phase
Pm Protective earth
8-36 VDC DCIN Plus
XGND Minus

RS485 weather sensors

Use RS485 for supported driver instruments. Configure the driver model and communication settings before configuring DataGuard reporting.

Port A B Signal ground
RS485 port 1 485_1_A 485_1_B 485_SGND
RS485 port 2 485_2_A 485_2_B 485_SGND

Analog weather inputs

Use analog inputs for validated 4-20 mA or 0-10 V transmitters. Viking default for AI1-AI2 is 4-20 mA with JPAI1-JPAI2 installed.

Input Terminals Default signal Use
AI1 AI1-AGND 4-20 mA transmitter; JPAI1 installed. Project weather or climate value.
AI2 AI2-AGND 4-20 mA transmitter; JPAI2 installed. Project weather or climate value.

Use Analog Transmitter Wiring before configuring the DataGuard analog reporting parameters.

Digital and counter inputs

Use digital input or counter wiring only when the connected instrument and delivered setup support the required WeatherStation value.

Input Terminals Signal Typical use
DI1-DI4 DI#-GND S0/NPN with JPDI# in position S. Pulse or contact instruments such as rain gauges when configured.
DI5 DI5-DCOUT PNP/positive input; no JPDI jumper. Positive input instruments when specified.

1-Wire inputs

Use 1-Wire for simple temperature measurement where the delivered WeatherStation setup includes a 1-Wire temperature sensor.

Terminal Use Condition
1Wire 1-Wire bus Use with 1-Wire Temperature Monitoring.
SGND Signal ground Required bus reference.

Hardware jumper reference

Jumper Function Viking default Change when
JPDI1-JPDI4 DI1-DI4 input type. Position S = S0/NPN-style input. The connected digital signal is PNP/normal positive input.
JPAI1-JPAI2 AI1-AI2 input type. Installed for 4-20 mA transmitter use. Hardware range is 0-20 mA. The transmitter nameplate/datasheet specifies 0-10 V voltage output.
TER1 / TER2 RS485 endpoint termination. Installed = 120 ohm termination enabled. The port is not at a physical end of the RS485 bus.
JP101 DCOUT voltage. 24 V DC-Out. The connected equipment nameplate/datasheet requires 12 V DC-Out.

Public revision 21/08/2026