FlexGuard NX 910 IODigital input/output. list

Terminal lists and jumper settings for FlexGuard NX 910.

NX 910

Controller Mounting Supply voltage Digital inputs Relay outputs Analogue inputs Analogue inputs

Model: NX 910

Wall mounting 8-36 VDC or 230 VAC 5 4 2 0

Supply voltage

Supply voltage Terminal Use Note
230VAC P L1 (100-260VAC / 50/60 Hz) 12/24 V and 230 V can be connected at the same time
N Neutral
Protective earth
8-36 VDC DCIN Plus
XGND Minus

Digital inputs

Digital inputs Terminal Use Note
Input 1 DI1

If jumper JPDI1 is in position N, the signal on DI1 must be 8-40 VDC (PNPPNP is a positive signal (plus).)

If jumper JPDI1 is in position S, the signal must be between GND and DI1 (S0IEC 62053-31 Class A S0 standard for pulse signals./NPNNPN is a negative signal (minus).)

Use PNPPNP is a positive signal (plus). or NPNNPN is a negative signal (minus). signal
Input 2 DI2

If jumper JPDI2 is in position N, the signal on DI2 must be 8-40 VDC (PNPPNP is a positive signal (plus).)

If jumper JPDI2 is in position S, the signal must be between GND and DI2 (S0IEC 62053-31 Class A S0 standard for pulse signals./NPNNPN is a negative signal (minus).)

Input 3 DI3

If jumper JPDI3 is in position N, the signal on DI3 must be 8-40 VDC (PNPPNP is a positive signal (plus).)

If jumper JPDI3 is in position S, the signal must be between GND and DI3 (S0IEC 62053-31 Class A S0 standard for pulse signals./NPNNPN is a negative signal (minus).)

Input 4 DI4

If jumper JPDI4 is in position N, the signal on DI4 must be 8-40 VDC (PNPPNP is a positive signal (plus).)

If jumper JPDI4 is in position S, the signal must be between GND and DI4 (S0IEC 62053-31 Class A S0 standard for pulse signals./NPNNPN is a negative signal (minus).)

Input 5 DI5 The signal on DI5 must be 8-40 VDC (PNPPNP is a positive signal (plus).) Use only PNPPNP is a positive signal (plus). signal
Ground GND Ground for inputs 1..5 Must always be connected

Relay outputs

Relay outputs Terminal Use Note
Output 1 R1A and R1B Contact set 1, NONormally open. Max. 5A @ 250VAC / 30 VDC
Output 2 R2A and R2B Contact set 2, NONormally open.
Output 3 R3A and R3B Contact set 3, NONormally open.
Output 4 R4A and R4B Contact set 4, NONormally open.

Analogue inputs

Analogue inputs Terminal Use Note
Input 1 AI1

If jumper JPAI1 is not installed, a 0-10 V signal is used on AI1

If jumper JPAI1 is installed, a 4-20 mA signal is used on AI1

Connect the transmitter between AINx and AGND using 0-10 V or 4-20 mA
Input 2 AI2

If jumper JPAI2 is not installed, a 0-10 V signal is used on AI2

If jumper JPAI2 is installed, a 4-20 mA signal is used on AI2

Ground AGND Ground for analogue inputs Must always be connected to the transmitter reference point (ground)

RS232 port 1

RS232 communication Terminal Use Note
Port 1 SER1_TXD

Transmits data

-

SER1_RXD

Receives data

Ground SGND Ground for RS232

RS232 port 2

RS232 communication Terminal Use Note
Port 2 SER2_TXD

Transmits data

RS232 port with RTS/CTS handshaking signals
SER2_RXD

Receives data

SER2_CTS Clear to send
SER2_RTS Request to send
Ground SGND Ground for RS232

RS485 port 1

RS485 communication Terminal Use Note
Port 1

RS485_1+

RS485 non-inverting signal (A)

Install jumper TER1 to activate a 120 ohm resistor on the bus

Read more about termination here

RS485_1-

RS485 inverting signal (B)

Ground SGND Ground for RS485

RS485 port 2

RS485 communication Terminal Use Note
Port 2

RS485_2+

RS485 non-inverting signal (A)

Install jumper TER2 to activate a 120 ohm resistor on the bus

Read more about termination here

RS485_2-

RS485 inverting signal (B)

Ground SGND Ground for RS485

1-Wire

1-Wire communication Terminal Use Note
Port 1 1Wire 1-Wire bus

Connect the equipment between 1Wire and SGND

1Wire-LED 1-Wire ID button with LED lamp
Ground SGND Ground for 1-Wire

Ethernet

Ethernet communication Terminal Use Note
100BASE-T RJ45 -

-

DC outputs

DC outputs Terminal Use Note
DC output 5 VDC, max. 300 mA DCOUT5 Extra 3.3 VDC supply voltage, max. 300 mA Use the jumper in the middle on the right side to select between 12 V or 24 V DC output
DC output 12/24 VDC, max. 500/250 mA DCOUT Extra 12/24 VDC supply voltage, max. 500 mA at 12 V and max. 250 mA at 24 V
Ground SGND Ground for DC

Public revision 21/08/2026