Use this page as the pump-wiring, terminal, interface, and jumper reference for FlexVander LX4 pro. The LX4 pro controller provides the physical inputs, outputs, and communication interfaces used by the FlexVander pump program and optional installed functions.
| Controller type | Mounting | Supply voltage | Ingress protection |
| LX4 pro controller | 9 Module M36 DIN-rail encapsulation | 8-36 VDC | IP20 |
The physical size is W 157 x H 86 x D 58 mm without SMA connector and screw terminals.
For basic FlexVander operation, connect the LX4 controller supply, digital output supply, pump-control outputs, and operating-status feedback for each installed pump. Select the wiring table that matches the FlexVander program used on the installation.
| Supply | Terminals | Use | Note |
| Controller supply | 28/29 SUPP, 27 PGND | 8-36 VDC supply to the LX4 controller. | The two SUPP terminals are tied together internally. |
| Digital output supply | 30 DOUT SUPP, 39 DOUT GND | External DC supply for the digital outputs. | DOUT SUPP is not internally connected to SUPP. |
The LX4 digital outputs are protected high-side DC outputs. They are not potential-free relay contacts. Use an interface relay when the pump control circuit needs a potential-free contact set.
Program 1 controls one or two pressure pumps without a submersible pump. Required for basic operation: start/stop outputs and operating-status feedback for each installed pressure pump.
The digital outputs send the FlexVander start and stop signals. FVADOUTT# sets the start-output pulse/hold time. The output is not a potential-free relay contact; install an interface relay when the pump panel requires a relay contact.
| Output | Function | LX4 terminal | Condition |
| Output 1 | Start pressure pump 1 | 31 DOUT1 | Required |
| Output 2 | Start pressure pump 2 | 32 DOUT2 | If pressure pump 2 is installed |
| Output 3 | Stop pressure pump 1 | 33 DOUT3 | Required |
| Output 4 | Stop pressure pump 2 | 34 DOUT4 | If pressure pump 2 is installed |
Stop output behaviour can be changed with DWCONTACT# when the installation requires NC behaviour. On LX4, this changes the FlexVander output behaviour; it does not turn the high-side output into a potential-free NC contact.
FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.
Connect each pump-running feedback signal to the listed LX4 input with SGND as reference. In the default setup, use a PNP/normal positive input signal. Set the relevant DIN jumper to Position S only when the installed signal is S0/NPN/contact style.
| Input | Pump | LX4 terminals | Signal | Condition |
| Input 2 | Pressure pump 1 | 42 DIN2, 40 or 49 SGND | PNP / normal positive input; DIN2 Position N. | Required |
| Input 3 | Pressure pump 2 | 43 DIN3, 40 or 49 SGND | PNP / normal positive input; DIN3 Position N. | If pressure pump 2 is installed |
Program 2 controls one submersible pump and one or two pressure pumps. Required for basic operation: start/stop outputs and operating-status feedback for each installed pump.
The digital outputs send the FlexVander start and stop signals. FVADOUTT# sets the start-output pulse/hold time. The output is not a potential-free relay contact; install an interface relay when the pump panel requires a relay contact.
| Output | Function | LX4 terminal | Condition |
| Output 1 | Start submersible pump | 31 DOUT1 | Required |
| Output 2 | Start pressure pump 1 | 32 DOUT2 | Required |
| Output 3 | Start pressure pump 2 | 33 DOUT3 | If pressure pump 2 is installed |
| Output 4 | Stop all pumps | 34 DOUT4 | Required |
Stop output behaviour can be changed with DWCONTACT# when the installation requires NC behaviour. On LX4, this changes the FlexVander output behaviour; it does not turn the high-side output into a potential-free NC contact.
FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.
Connect each pump-running feedback signal to the listed LX4 input with SGND as reference. In the default setup, use a PNP/normal positive input signal. Set the relevant DIN jumper to Position S only when the installed signal is S0/NPN/contact style.
| Input | Pump | LX4 terminals | Signal | Condition |
| Input 1 | Submersible pump | 41 DIN1, 40 or 49 SGND | PNP / normal positive input; DIN1 Position N. | Required |
| Input 2 | Pressure pump 1 | 42 DIN2, 40 or 49 SGND | PNP / normal positive input; DIN2 Position N. | Required |
| Input 3 | Pressure pump 2 | 43 DIN3, 40 or 49 SGND | PNP / normal positive input; DIN3 Position N. | If pressure pump 2 is installed |
Stop-circuit note: when a stop circuit must not depend directly on the LX4 high-side output, use a normally-open FlexVander output to drive an interposing relay and use the relay's NC contact in the stop circuit.
Local push buttons are optional physical inputs for local pump operation at the installation. Use FVALOCIN to select the digital input used for the local push button.
FVALOCIN 0 disables local push-button operation. Values 1 to 8 select LX4 digital inputs 1 to 8.
Use only an input that is available on the installed LX4 pro and not already used for pump feedback or another installed function.
For DIN1 to DIN4, the default setting is Position N for PNP/normal positive input. Use Position S only when the local button signal is wired as S0/NPN/contact style.
FVALOCIN value |
LX4 input | Terminals | Signal / jumper | Note |
| 1 | Digital input 1 | 41 DIN1, 40 or 49 SGND | PNP / normal positive input; Position N default. | Do not use if input 1 is used for Program 2 submersible pump feedback. |
| 2 | Digital input 2 | 42 DIN2, 40 or 49 SGND | PNP / normal positive input; Position N default. | Do not use if input 2 is used for pressure pump 1 feedback. |
| 3 | Digital input 3 | 43 DIN3, 40 or 49 SGND | PNP / normal positive input; Position N default. | Do not use if input 3 is used for pressure pump 2 feedback. |
| 4 | Digital input 4 | 44 DIN4, 40 or 49 SGND | PNP / normal positive input; Position N default. | Use only when input 4 is not assigned to another function. |
| 5 | Digital input 5 | 45 DIN5, 40 or 49 SGND | Normal positive input; no S0 jumper. | Use only when input 5 is not assigned to another function. |
| 6 | Digital input 6 | 46 DIN6, 40 or 49 SGND | Normal positive input; no S0 jumper. | Use only when input 6 is not assigned to another function. |
| 7 | Digital input 7 | 47 DIN7, 40 or 49 SGND | Normal positive input; no S0 jumper. | Use only when input 7 is not assigned to another function. |
| 8 | Digital input 8 | 48 DIN8, 40 or 49 SGND | Normal positive input; no S0 jumper. | Use only when input 8 is not assigned to another function. |
FlexVander LX4 pro can be installed with or without pressure control. If pressure control is used, connect the pressure transmitter to the relevant analog input and configure Pressure Control Settings.
AIN1 is used for pressure line 1, and AIN2 is used for pressure line 2 when separate pressure transmitters are part of the solution. LX4 analog inputs are voltage inputs by default; install the relevant analog-input jumper when the transmitter signal is a current signal.
| Input | Pressure line | Terminals | Signal |
| Analog input 1 | Pressure line 1 | 22 AIN1, 26 AGND | 0-10 VDC or 0-20 mA, depending on jumper setting. |
| Analog input 2 | Pressure line 2 | 23 AIN2, 26 AGND | 0-10 VDC or 0-20 mA, depending on jumper setting. |
Before commissioning, verify the transmitter nameplate/datasheet and the selected input setup. Use AIN2 only when separate pressure line 2 measurement is part of the solution.
Use RS485 for energy meters when energy metering is part of the installation. Use Emiko-branded meters first where possible. See Energy Meters in Device Model for supported energy meters.
| Node | Meter for | Condition |
100 |
Submersible pump | Use only when a submersible pump is installed. |
101 |
Pressure pump 1 | Use only when pressure pump 1 has its own meter. |
102 |
Pressure pump 2 | Use only when pressure pump 2 has its own meter. |
| Port | Terminals | Note |
| RS485 port 1 | 9 RSA 1, 10 RSB 1, 8 SGND | Use shielded cable and terminate the bus at both physical endpoints. |
| RS485 port 2 | 12 RSA 2, 13 RSB 2, 11 SGND | Use only when the delivered solution assigns the energy meter bus to port 2. |
Use the controller interfaces below only when the FlexVander installation includes matching sensors and DataGuard reporting.
| Sensor path | Interface | Terminals | Installer note |
| Analog level or pressure sensor | Analog input | AIN1-AIN4 and AGND |
Use only if the input is not already assigned to pump pressure control. |
| Temperature or ID accessory | 1-Wire | 1Wire, 1Wire-LED, SGND |
Use the accessory wiring supplied with the sensor. |
| Weather or level instrument | RS485 | RSA1/RSB1 or RSA2/RSB2 with SGND |
Use when the instrument is a supported RS485 device on the FlexVander installation. |
See Climate and level sensors for supported serial instruments.
| Interface | Terminals | Use | Continue |
| Controller supply | 27 PGND, 28 SUPP, 29 SUPP | 8-36 VDC supply to the controller. | Controller supply. |
| Digital outputs | 30 DOUT SUPP, 31-38 DOUT1-DOUT8, 39 DOUT GND | Required pump start and stop outputs, plus other installed output functions. | Program 1, Program 2, and Digital outputs. |
| Digital inputs | 40 SGND, 41-48 DIN1-DIN8, 49 SGND | Required pump operating-status feedback and optional local push buttons. | Digital inputs and Local push buttons. |
| Analog inputs | 22-25 AIN1-AIN4, 26 AGND | Pressure transmitter input when pressure control is installed. | Pressure control and Analog inputs. |
| RS485 | 9 RSA 1, 10 RSB 1, 8 SGND; 12 RSA 2, 13 RSB 2, 11 SGND | RS485 devices such as energy meters and selected field devices. | RS485 energy metering and Communication interfaces. |
| 1-Wire | 5 SGND, 6 1-Wire, 7 1-Wire LED | Optional accessories such as ID-Button or temperature sensor. | Communication interfaces. |
| M-Bus | 18 M-BUS+, 19 M-BUS-/SGND | Wired M-Bus interface when required by the delivered solution. | Communication interfaces. |
| Pin | Name | Description |
| 5 | SGND | Signal ground. |
| 6 | 1-Wire | 1-Wire bus for accessories such as ID-Button or temperature sensor. |
| 7 | 1-Wire LED | 1-Wire ID-Button LED. |
| 8 | SGND | Signal ground. |
| 9 | RSA 1 | RS485 non-inverting signal for RS485 port 1. |
| 10 | RSB 1 | RS485 inverting signal for RS485 port 1. |
| 11 | SGND | Signal ground. |
| 12 | RSA 2 | RS485 non-inverting signal for RS485 port 2. |
| 13 | RSB 2 | RS485 inverting signal for RS485 port 2. |
| 14 | TXD | Transmit data for the RS232 port. |
| 15 | RXD | Receive data for the RS232 port. |
| 16 | RTS | Request to send for the RS232 port. |
| 17 | CTS | Clear to send for the RS232 port. |
| 18 | M-BUS+ | M-Bus signal. |
| 19 | M-BUS-/SGND | M-Bus ground / signal ground. |
| 20 | AOUT1 | Analog output 1. |
| 21 | AOUT2 | Analog output 2. |
| 22 | AIN1 | Analog input 1. |
| 23 | AIN2 | Analog input 2. |
| 24 | AIN3 | Analog input 3. |
| 25 | AIN4 | Analog input 4. |
| 26 | AGND | Analog ground. |
| 27 | PGND | Power ground, negative connection. |
| 28 | SUPP | Power supply, positive connection. |
| 29 | SUPP | Power supply, positive connection. |
| 30 | DOUT SUPP | Power supply for the digital outputs. |
| 31 | DOUT1 | Digital output 1. |
| 32 | DOUT2 | Digital output 2. |
| 33 | DOUT3 | Digital output 3. |
| 34 | DOUT4 | Digital output 4. |
| 35 | DOUT5 | Digital output 5. |
| 36 | DOUT6 | Digital output 6. |
| 37 | DOUT7 | Digital output 7. |
| 38 | DOUT8 | Digital output 8. |
| 39 | DOUT GND | Digital output ground. |
| 40 | SGND | Signal ground. |
| 41 | DIN1 | Digital input 1. Default is PNP/normal positive input. Position S can be used for S0 input 1. |
| 42 | DIN2 | Digital input 2. Default is PNP/normal positive input. Position S can be used for S0 input 2. |
| 43 | DIN3 | Digital input 3. Default is PNP/normal positive input. Position S can be used for S0 input 3. |
| 44 | DIN4 | Digital input 4. Default is PNP/normal positive input. Position S can be used for S0 input 4. |
| 45 | DIN5 / IGN | Digital input 5. |
| 46 | DIN6 | Digital input 6. |
| 47 | DIN7 | Digital input 7. |
| 48 | DIN8 | Digital input 8. |
| 49 | SGND | Signal ground. |
The controller must be supplied with 8-36 VDC from an external DC power source. Positive power is applied to SUPP and ground to PGND. The two SUPP terminals are tied together internally.
| Pin | Name | Use |
| 27 | PGND | Power ground, negative connection. |
| 28 | SUPP | Power supply, positive connection. |
| 29 | SUPP | Power supply, positive connection. |
PGND should only be connected to the external DC power source. SGND, DOUT GND, and AGND are filtered from the supply ground and tied together internally.
If a chassis or system ground is connected to SGND or AGND, wrong polarity on the supply lines can damage the internal ground connection.
The eight digital outputs are protected high-side switches. The digital output control circuit is supplied from DOUT SUPP and DOUT GND. DOUT SUPP is not internally connected to SUPP and needs an external DC power source.
| Pin | Name | Use |
| 30 | DOUT SUPP | Digital output supply, positive connection. |
| 31-38 | DOUT1-DOUT8 | Digital outputs 1 to 8. |
| 39 | DOUT GND | Digital output ground, negative connection. |
The digital inputs are low-pass filtered and transient protected. To activate an input, connect a positive voltage between the input and SGND.
DIN1 to DIN4 can be configured individually as normal digital inputs or S0 inputs.Position N: PNP/normal positive input.Position S selects S0/NPN/contact input style for the relevant input.S0IN1 means S0 input 1: the S0 pulse-input mode of the same physical terminal as DIN1.SGND.DIN6 to DIN8 do not work as high-speed IO.| Pin | Name | Use |
| 40 | SGND | Signal ground. |
| 41 | DIN1 | Digital input 1. Default is PNP/normal positive input. The same terminal can be configured as S0 input 1 with Position S. |
| 42 | DIN2 | Digital input 2. Default is PNP/normal positive input. The same terminal can be configured as S0 input 2 with Position S. |
| 43 | DIN3 | Digital input 3. Default is PNP/normal positive input. The same terminal can be configured as S0 input 3 with Position S. |
| 44 | DIN4 | Digital input 4. Default is PNP/normal positive input. The same terminal can be configured as S0 input 4 with Position S. |
| 45 | DIN5 / IGN | Digital input 5. |
| 46-48 | DIN6-DIN8 | Digital inputs 6 to 8. |
| 49 | SGND | Signal ground. |
Logic high is 8-40 VDC. Logic low is -5 to 3 VDC.
The controller has four analog inputs. Each input can be configured for voltage measurement or current measurement with hardware jumpers. Inputs are voltage inputs by default.
| Pin | Name | Use |
| 22-25 | AIN1-AIN4 | Analog inputs 1 to 4. |
| 26 | AGND | Analog ground. |
AINx and AGND.The controller has two analog outputs. Each output can be configured for voltage output or current output with hardware jumpers. Outputs are voltage outputs by default.
| Pin | Name | Use |
| 20-21 | AOUT1-AOUT2 | Analog outputs 1 to 2. |
| 26 | AGND | Analog ground. |
AOUTx and AGND.The RS232 port is a general-purpose serial port with hardware handshake signals.
| Pin | Name | Use |
| 11 | SGND | Signal ground. |
| 14-17 | TXD, RXD, RTS, CTS | RS232 transmit, receive, request-to-send, and clear-to-send signals. |
RS485 is a multi-drop network with up to 32 nodes on one bus. Connect RSA, RSB, and the common signal ground for all nodes on the bus. Use shielded cable for best performance, protection, and noise immunity.
| Port | Pins | Use |
| RS485 port 1 | 9 RSA 1, 10 RSB 1, 8 SGND | Port 1 is available on the pluggable screw terminals and is not shared with other sources. |
| RS485 port 2 | 12 RSA 2, 13 RSB 2, 11 SGND | Port 2 is available on the pluggable screw terminals and is not shared with other sources. |
If the controller is used as an RS485 endpoint, install the relevant RS485 termination jumper to enable the onboard 120 ohm line termination resistor. RS485 termination is not installed by default.
The 1-Wire bus is available on the pluggable screw terminals for accessories such as ID-Button or temperature sensor.
| Pin | Name | Use |
| 5 | SGND | Signal ground. |
| 6 | 1-Wire | 1-Wire bus. |
| 7 | 1-Wire LED | 1-Wire ID-Button LED. |
The specified 1-Wire bus total weight is 65 m.
The wired M-Bus interface is compliant with EN 13757-2/3 and supports communication with up to 20 slave nodes. The M-Bus interface needs an external supply to be operational.
| Pin | Name | Use |
| 18 | M-BUS+ | M-Bus signal. |
| 19 | M-BUS-/SGND | M-Bus ground / signal ground. |
Open the controller only when internal access is required. Remove the SD card and USB cable before opening the enclosure.
| Jumper | Function | Default | Other setting | Note |
| RS485 TERM1 | Enable or disable 120 ohm line termination for RS485 port 1. | Not installed | Installed = termination enabled. | Install only when port 1 is an RS485 endpoint. |
| RS485 TERM2 | Enable or disable 120 ohm line termination for RS485 port 2. | Not installed | Installed = termination enabled. | Install only when port 2 is an RS485 endpoint. |
| Ain 1-Ain 4 | Analog input mode. | Not installed | Installed = current input mode. | Default is voltage input mode. |
| Aout 1-Aout 2 | Analog output mode. | Position V | Position C = current output. | Position V = voltage output. |
| Din 1-Din 4 | Digital input mode. | Position N = PNP / normal positive input. | Position S = S0/NPN/contact input. | Change each input individually only when the installed signal requires it. |
Public revision 21/08/2026