FlexVander LX4 pro installation

FlexVander LX4 pro is the current DIN-rail model for installations where the controller is mounted in an electrical cabinet. This installation page gives the controller wiring flow; the IO list gives the terminal, interface, and jumper reference.

Installation choices

Use this page for the controller hardware installation and the FlexVander pump-control wiring flow. Select the pump program before wiring the pump panel.

Before wiring

Supply wiring

The controller must be supplied with 8-36 VDC from an external DC power source. Connect positive supply to SUPP and negative supply to PGND.

Connection Terminal Use
Negative supply 27 - PGND Power ground, negative connection.
Positive supply 28 - SUPP Power supply, positive connection.
Positive supply 29 - SUPP Power supply, positive connection. The two SUPP terminals are tied together internally.

Keep PGND for the external DC power source connection. Signal ground, digital output ground, and analog ground are filtered from the supply ground and tied together internally. For signal wiring, choose the SGND terminal closest to the signal terminal for best noise immunity.

Digital output supply

The digital output control circuit is supplied separately through DOUT SUPP and DOUT GND. DOUT SUPP is not internally connected to SUPP and must be connected to the intended external DC power source when digital outputs are used.

Signal and interface wiring

Wire only the interfaces required by the delivered solution. FlexVander uses digital outputs for pump commands and digital inputs for pump operating feedback. Output pulse time is set with FVADOUTT#, and stop output behaviour can be changed with DWCONTACT# where supported by the installation.

Pressure control

When pressure control is installed, connect the pressure transmitter to the analog input listed in Pressure control. Configure the analog input jumper for the transmitter signal type before commissioning.

Use FVAPRESS, FVAPTRMODE, and FVAPRESSDELAY1/2 for the FlexVander pressure functions.

Energy consumption registration

When an RS485 energy meter is installed, connect it to the RS485 port selected for the project and terminate the RS485 line only at the two physical endpoints. See the energy metering section for the terminal reference.

Mini Weather Station

Connect supported weather and level sensors through the available analog, 1-Wire, or RS485 interface according to the sensor type. Use the mini weather station section as the controller-side terminal reference.

Jumper and service checks

Hardware jumpers are inside the controller. Check the required jumper positions before commissioning.

Before handover

IO list

See the FlexVander LX4 pro IO list for terminal, interface, and jumper details.