FlexVander LX4 pro is the current DIN-rail model for installations where the controller is mounted in an electrical cabinet. This installation page gives the controller wiring flow; the IO list gives the terminal, interface, and jumper reference.
Use this page for the controller hardware installation and the FlexVander pump-control wiring flow. Select the pump program before wiring the pump panel.
The controller must be supplied with 8-36 VDC from an external DC power source. Connect positive supply to SUPP and negative supply to PGND.
| Connection | Terminal | Use |
| Negative supply | 27 - PGND | Power ground, negative connection. |
| Positive supply | 28 - SUPP | Power supply, positive connection. |
| Positive supply | 29 - SUPP | Power supply, positive connection. The two SUPP terminals are tied together internally. |
Keep PGND for the external DC power source connection. Signal ground, digital output ground, and analog ground are filtered from the supply ground and tied together internally. For signal wiring, choose the SGND terminal closest to the signal terminal for best noise immunity.
The digital output control circuit is supplied separately through DOUT SUPP and DOUT GND. DOUT SUPP is not internally connected to SUPP and must be connected to the intended external DC power source when digital outputs are used.
30 - DOUT SUPP.39 - DOUT GND.Wire only the interfaces required by the delivered solution. FlexVander uses digital outputs for pump commands and digital inputs for pump operating feedback. Output pulse time is set with FVADOUTT#, and stop output behaviour can be changed with DWCONTACT# where supported by the installation.
SGND.DIN1 to DIN4 can be configured as normal digital inputs or S0 inputs with hardware jumpers.AINx and AGND. Inputs can be configured for 0-10 VDC or 0-20 mA.AOUTx and AGND. Outputs can be configured for 0-10 VDC or 0-20 mA.When pressure control is installed, connect the pressure transmitter to the analog input listed in Pressure control. Configure the analog input jumper for the transmitter signal type before commissioning.
Use FVAPRESS, FVAPTRMODE, and FVAPRESSDELAY1/2 for the FlexVander pressure functions.
When an RS485 energy meter is installed, connect it to the RS485 port selected for the project and terminate the RS485 line only at the two physical endpoints. See the energy metering section for the terminal reference.
Connect supported weather and level sensors through the available analog, 1-Wire, or RS485 interface according to the sensor type. Use the mini weather station section as the controller-side terminal reference.
Hardware jumpers are inside the controller. Check the required jumper positions before commissioning.
DIN1 to DIN4 select S0 mode or normal digital input mode.SGND, AGND, or DOUT GND.See the FlexVander LX4 pro IO list for terminal, interface, and jumper details.