Use this page as the terminal and jumper reference for FlexVander LX9 pro. The built-in controller is VikMote LX9 pro.
| Controller | Mounting | Supply voltage | Dimensions |
| VikMote LX9 pro | Wall mounting, polycarbonate enclosure, IP65 | 100-260 VAC or 8-36 VDC | W 130 x H 180 x D 60 mm; approx. 690 g without accessories |
| Group | Available hardware |
| Digital I/O | 5 digital inputs, DI1-DI4 as S0-capable inputs, and 4 normally-open relay outputs. |
| Analog I/O | 4 analog inputs and 4 analog outputs. Each analog channel supports 0-10 VDC or 0-20 mA hardware mode. |
| Communication | 2 RS232 ports, 2 RS485 ports, 1-Wire, Ethernet, LTE Cat.4 cellular, Wi-Fi, Bluetooth LE, and GNSS. |
| DC outputs | 5 V DC-Out, 12 V DC-Out, and 24 V DC-Out for supported external equipment. |
| Battery | On-board 2 Ah Li-Ion backup battery with intelligent charger. |
For basic FlexVander operation, connect supply, pump relay outputs, and operating-status feedback for each installed pump. Select the wiring table that matches the FlexVander program used on the installation.
| Supply | Terminal | Use | Note |
| 100-260 VAC | N | Neutral | VAC and VDC supply can be connected at the same time. |
| P | Phase | ||
| Pm | Protective earth | ||
| 8-36 VDC | DCIN | Plus | |
| XGND | Minus |
Program 1 controls one or two pressure pumps without a submersible pump. Required for basic operation: start and stop relay outputs and operating-status feedback for each installed pressure pump.
The relay outputs send pulses to the pump start and stop circuits. The output is not held active while the pump runs; pump running must be maintained by the pump control circuit, contactor, or holding circuit. Pulse time is configured with FVADOUTT#.
Relay outputs are normally-open contact sets. Maximum relay load is 5 A @ 250 VAC / 30 VDC. There are no internal connections to the relay outputs; wire the switched source through the listed terminal pair.
| Output | Function | Terminals | Condition |
| Output 1 | Start pressure pump 1 | R1A-R1B | Required |
| Output 2 | Start pressure pump 2 | R2A-R2B | If pressure pump 2 is installed |
| Output 3 | Stop pressure pump 1 | R3A-R3B | Required |
| Output 4 | Stop pressure pump 2 | R4A-R4B | If pressure pump 2 is installed |
Stop outputs can be changed to NC behavior with DWCONTACT# when the installation requires it.
FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.
With the Viking default JPDI1-JPDI4 = Position S, connect each pump-running contact across the listed terminals. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
| Input 2 | Pressure pump 1 | DI2-GND | S0/NPN; JPDI2 = S. | Required |
| Input 3 | Pressure pump 2 | DI3-GND | S0/NPN; JPDI3 = S. | If pressure pump 2 is installed |
Program 2 controls one submersible pump and one or two pressure pumps. Required for basic operation: start and stop relay outputs and operating-status feedback for each installed pump.
The relay outputs send pulses to the pump start and stop circuits. The output is not held active while the pump runs; pump running must be maintained by the pump control circuit, contactor, or holding circuit. Pulse time is configured with FVADOUTT#.
Relay outputs are normally-open contact sets. Maximum relay load is 5 A @ 250 VAC / 30 VDC. There are no internal connections to the relay outputs; wire the switched source through the listed terminal pair.
| Output | Function | Terminals | Condition |
| Output 1 | Start submersible pump | R1A-R1B | Required |
| Output 2 | Start pressure pump 1 | R2A-R2B | Required |
| Output 3 | Start pressure pump 2 | R3A-R3B | If pressure pump 2 is installed |
| Output 4 | Stop all pumps | R4A-R4B | Required |
Stop outputs can be changed to NC behavior with DWCONTACT# when the installation requires it.
FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.
With the Viking default JPDI1-JPDI4 = Position S, connect each pump-running contact across the listed terminals. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
| Input 1 | Submersible pump | DI1-GND | S0/NPN; JPDI1 = S. | Required |
| Input 2 | Pressure pump 1 | DI2-GND | S0/NPN; JPDI2 = S. | Required |
| Input 3 | Pressure pump 2 | DI3-GND | S0/NPN; JPDI3 = S. | If pressure pump 2 is installed |
Stop-circuit note: NC output mode depends on the FlexVander controller being powered and functioning. For stop circuits that must not depend directly on the controller, use a normally-open FlexVander output to drive an interposing relay and use the relay's NC contact in the stop circuit.
| Interface | Terminals | Use | Continue |
| Relay outputs | R1A/R1B to R4A/R4B | Required pump start and stop outputs. | Program 1 or Program 2. |
| Digital inputs | DI1-DI4 and GND; DI5 positive input referenced to GND | Required pump operating-status feedback and optional local push buttons. | Program feedback tables and Local push buttons. |
| Analog inputs | AI1-AI4 and AGND | Pressure transmitters and optional analog field sensors. | Pressure control, Additional analog inputs, and Analog Transmitter Wiring. |
| Analog outputs | AO1-AO4 and AGND | Available hardware for cabinet-specific setup only. | Follow the cabinet documentation before connecting analog output control signals. |
| RS232 | SER1_TXD/SER1_RXD/SGND; SER2_TXD/SER2_RXD/SER2_CTS/SER2_RTS/SGND | Available hardware for cabinet-specific setup only. | Follow the cabinet documentation before connecting serial instruments. |
| RS485 | 485_1A/485_1B/485_SGND and 485_2A/485_2B/485_SGND | RS485 equipment such as energy meters and selected cabinet-specific sensors. | RS485 energy metering and Mini Weather Station sensors. |
| M-Bus | Not available on LX9 pro | Not used. | Use a model with M-Bus support if M-Bus is required. |
| 1-Wire | 1Wire, 1Wire-LED, and SGND | Optional temperature measurement, for example soil temperature. | 1-Wire options. |
| DC outputs | DCOUT5-SGND and DCOUT-SGND | 5 V, 12 V, or 24 V supply for supported external equipment. | DC outputs. |
| Ethernet | RJ45 | Available hardware for cabinet-specific setup only. | Follow the cabinet documentation before using Ethernet in FlexVander. |
Local push buttons are optional physical inputs for local pump operation at the installation. Use FVALOCIN to select which digital input is used for the local push button.
| Input | Function | Terminals | Signal | Condition |
| Input 1 | Local push button | DI1-GND | S0/NPN; JPDI1 = S. | Program 1 only |
| Input 4 | Local push button | DI4-GND | S0/NPN; JPDI4 = S. | DI4 not assigned to another function |
| Input 5 | Local push button | DI5-DCOUT | PNP/positive input referenced to GND; no JPDI jumper or S0 mode. | Use a positive feed; GND is the input reference. |
FlexVander LX9 pro can be installed with or without pressure control. If pressure control is used, connect the pressure transmitter to the relevant analog input and configure Pressure Control Settings.
AI1 is shown as Pressure line 1 in Emiko, and AI2 is shown as Pressure line 2 when separate pressure transmitters are used. Viking default for AI1-AI2 is 4-20 mA with JPAI1-JPAI2 installed. See Analog Transmitter Wiring for 4-20 mA and 0-10 V wiring principles.
| Input | Pressure line | Terminals | Signal |
| Input 1 | Pressure line 1 | AI1-AGND | 4-20 mA transmitter; JPAI1 installed. |
| Input 2 | Pressure line 2 | AI2-AGND | 4-20 mA transmitter; JPAI2 installed. |
Before commissioning, verify the transmitter nameplate/datasheet and the selected input setup. Use AI2 only when separate pressure line 2 measurement is part of the solution.
Use RS485 for energy meters when energy metering is part of the installation. Use Emiko-branded meters first where possible. See Energy Meters in Device Model for supported energy meters.
| Node | Meter for | Condition |
100 |
Submersible pump | Use only when a submersible pump is installed. |
101 |
Pressure pump 1 | Use only when pressure pump 1 has its own meter. |
102 |
Pressure pump 2 | Use only when pressure pump 2 has its own meter. |
| Port | A | B | SGND |
| RS485 port 1 | 485_1A | 485_1B | 485_SGND |
| RS485 port 2 | 485_2A | 485_2B | 485_SGND |
485_SGND to the common signal ground for the equipment on the bus.TER1 enables endpoint termination for port 1 and TER2 enables endpoint termination for port 2.TER1 and TER2 are installed.Use DC outputs only when the delivered installation assigns them to supported external equipment. Check the connected equipment nameplate and the delivered setup before using the outputs.
| Output | Terminals | Rating | Condition |
| 5 V DC-Out | DCOUT5-SGND | 5 V / 300 mA | Use only when included in the delivered setup. |
| 12 V DC-Out | DCOUT-SGND | 12 V / 500 mA | Use only when selected with JP101 and the supply is at least 14 VDC. |
| 24 V DC-Out | DCOUT-SGND | 24 V / 250 mA | Use only when selected with JP101 and the controller has AC supply. |
Use DataGuard when Mini Weather Station values or other field values must be logged or shown in Emiko. FlexVander documents the physical input; DataGuard documents how the selected value is reported and logged.
See Climate and Level Sensors for serial instruments, Analog Inputs, Digital Inputs and Counters, and 1-Wire Temperature.
The LX9 pro controller provides AI3 and AI4 for additional analog field sensors when the delivered setup assigns those inputs. The connected instrument nameplate or datasheet decides whether the input is configured for 4-20 mA or 0-10 V.
| Input | Terminals | Signal | Condition |
| Input 3 | AI3-AGND | 4-20 mA with JPAI3 installed; 0-10 V with JPAI3 not installed. | Only when assigned by the delivered setup. |
| Input 4 | AI4-AGND | 4-20 mA with JPAI4 installed; 0-10 V with JPAI4 not installed. | Only when assigned by the delivered setup. |
Use Instrument Families to select a supported serial instrument. Use the applicable Analog Inputs, Digital Inputs and Counters, or 1-Wire Temperature page for the other connection paths. If the instrument is not listed, use the cabinet documentation for the installed interface.
Use 1-Wire for temperature measurement where the installation needs simple field temperature values, for example soil temperature. Configure the 1-Wire channel first, then add DataGuard reporting if the value must be logged or shown in Emiko.
| Terminal | Use | Condition |
| 1Wire | 1-Wire bus | Use with 1-Wire Temperature Monitoring |
| SGND | Signal ground | Required bus reference |
| 1Wire-LED | ID-Button LED output | Not normally used for FlexVander field temperature sensors. |
The Viking defaults are the delivered FlexVander setup. Change a jumper only when the connected signal or instrument requires a different input type.
| Jumper | Function | Viking default | Other setting | Change when |
| JPDI1-JPDI4 | DI1-DI4 as NPN/S0-style inputs for local buttons and pump operating status. | Position S = S0/NPN-style input. | Position N = PNP/normal digital input. | Change only when the connected digital signal is PNP/normal positive input. |
| JPAI1-JPAI2 | AI1-AI2 input type. | Installed for 4-20 mA pressure transmitter use. Hardware range is 0-20 mA. | Not installed = voltage input, 0-10 V. | Change only when the transmitter nameplate/datasheet specifies 0-10 V voltage output. |
| JPAI3-JPAI4 | AI3-AI4 input type for optional analog field sensors. | Set by the delivered sensor setup. | Installed = current input, 0-20 mA. Not installed = voltage input, 0-10 V. | Change only when the connected instrument requires the other input type. |
| JPAO1-JPAO4 | AO1-AO4 output type. | Left as delivered unless analog outputs are part of the assisted setup. | Position V = voltage output, 0-10 V. Position C = current output, 0-20 mA. | Change only as part of an approved assisted setup. |
| TER1 | RS485 port 1 endpoint termination. | Installed = 120 ohm termination enabled. | Not installed = termination disabled. | Remove only when RS485 port 1 is not at a physical end of the bus. |
| TER2 | RS485 port 2 endpoint termination. | Installed = 120 ohm termination enabled. | Not installed = termination disabled. | Remove only when RS485 port 2 is not at a physical end of the bus. |
| JP101 | DCOUT voltage. | 24 V DC-Out | Position 12V = 12 V / 500 mA. Position 24V = 24 V / 250 mA. | Change only when the connected equipment nameplate/datasheet requires 12 V DC-Out. |
Public revision 21/08/2026