FlexVander LX9 pro IO list

Use this page as the terminal and jumper reference for FlexVander LX9 pro. The built-in controller is VikMote LX9 pro.

Hardware overview

Controller Mounting Supply voltage Dimensions
VikMote LX9 pro Wall mounting, polycarbonate enclosure, IP65 100-260 VAC or 8-36 VDC W 130 x H 180 x D 60 mm; approx. 690 g without accessories

Core hardware

Group Available hardware
Digital I/O 5 digital inputs, DI1-DI4 as S0-capable inputs, and 4 normally-open relay outputs.
Analog I/O 4 analog inputs and 4 analog outputs. Each analog channel supports 0-10 VDC or 0-20 mA hardware mode.
Communication 2 RS232 ports, 2 RS485 ports, 1-Wire, Ethernet, LTE Cat.4 cellular, Wi-Fi, Bluetooth LE, and GNSS.
DC outputs 5 V DC-Out, 12 V DC-Out, and 24 V DC-Out for supported external equipment.
Battery On-board 2 Ah Li-Ion backup battery with intelligent charger.

How to use this IO list

  1. Select the FlexVander pump program used on the installation.
  2. Wire the supply terminals.
  3. Wire the relay outputs for pump start and stop.
  4. Wire the operating-status feedback for each installed pump.
  5. Add only the optional features that are part of the delivered solution.
  6. Check the hardware jumper reference before commissioning.

Required basic pump wiring

For basic FlexVander operation, connect supply, pump relay outputs, and operating-status feedback for each installed pump. Select the wiring table that matches the FlexVander program used on the installation.

Supply voltage

Supply Terminal Use Note
100-260 VAC N Neutral VAC and VDC supply can be connected at the same time.
P Phase
Pm Protective earth
8-36 VDC DCIN Plus
XGND Minus

Program 1 basic wiring: one or two pressure pumps

Program 1 controls one or two pressure pumps without a submersible pump. Required for basic operation: start and stop relay outputs and operating-status feedback for each installed pressure pump.

Relay outputs

The relay outputs send pulses to the pump start and stop circuits. The output is not held active while the pump runs; pump running must be maintained by the pump control circuit, contactor, or holding circuit. Pulse time is configured with FVADOUTT#.

Relay outputs are normally-open contact sets. Maximum relay load is 5 A @ 250 VAC / 30 VDC. There are no internal connections to the relay outputs; wire the switched source through the listed terminal pair.

Output Function Terminals Condition
Output 1 Start pressure pump 1 R1A-R1B Required
Output 2 Start pressure pump 2 R2A-R2B If pressure pump 2 is installed
Output 3 Stop pressure pump 1 R3A-R3B Required
Output 4 Stop pressure pump 2 R4A-R4B If pressure pump 2 is installed

Stop outputs can be changed to NC behavior with DWCONTACT# when the installation requires it.

Required operating-status feedback

FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.

With the Viking default JPDI1-JPDI4 = Position S, connect each pump-running contact across the listed terminals. The signal must be active when the pump is running.

Input Pump Terminals Signal Condition
Input 2 Pressure pump 1 DI2-GND S0/NPNNPN is a negative signal (minus).; JPDI2 = S. Required
Input 3 Pressure pump 2 DI3-GND S0/NPNNPN is a negative signal (minus).; JPDI3 = S. If pressure pump 2 is installed

Program 2 basic wiring: submersible pump and one or two pressure pumps

Program 2 controls one submersible pump and one or two pressure pumps. Required for basic operation: start and stop relay outputs and operating-status feedback for each installed pump.

Relay outputs

The relay outputs send pulses to the pump start and stop circuits. The output is not held active while the pump runs; pump running must be maintained by the pump control circuit, contactor, or holding circuit. Pulse time is configured with FVADOUTT#.

Relay outputs are normally-open contact sets. Maximum relay load is 5 A @ 250 VAC / 30 VDC. There are no internal connections to the relay outputs; wire the switched source through the listed terminal pair.

Output Function Terminals Condition
Output 1 Start submersible pump R1A-R1B Required
Output 2 Start pressure pump 1 R2A-R2B Required
Output 3 Start pressure pump 2 R3A-R3B If pressure pump 2 is installed
Output 4 Stop all pumps R4A-R4B Required

Stop outputs can be changed to NC behavior with DWCONTACT# when the installation requires it.

Required operating-status feedback

FlexVander expects a feedback signal from each pump that has been started. If feedback is not detected after start, FlexVander stops the pump because it would otherwise run unmonitored. During operation, the same feedback input is used to detect that the pump has stopped.

With the Viking default JPDI1-JPDI4 = Position S, connect each pump-running contact across the listed terminals. The signal must be active when the pump is running.

Input Pump Terminals Signal Condition
Input 1 Submersible pump DI1-GND S0/NPNNPN is a negative signal (minus).; JPDI1 = S. Required
Input 2 Pressure pump 1 DI2-GND S0/NPNNPN is a negative signal (minus).; JPDI2 = S. Required
Input 3 Pressure pump 2 DI3-GND S0/NPNNPN is a negative signal (minus).; JPDI3 = S. If pressure pump 2 is installed

Stop-circuit note: NC output mode depends on the FlexVander controller being powered and functioning. For stop circuits that must not depend directly on the controller, use a normally-open FlexVander output to drive an interposing relay and use the relay's NC contact in the stop circuit.

Interface overview

Interface Terminals Use Continue
Relay outputs R1A/R1B to R4A/R4B Required pump start and stop outputs. Program 1 or Program 2.
Digital inputs DI1-DI4 and GND; DI5 positive input referenced to GND Required pump operating-status feedback and optional local push buttons. Program feedback tables and Local push buttons.
Analog inputs AI1-AI4 and AGND Pressure transmitters and optional analog field sensors. Pressure control, Additional analog inputs, and Analog Transmitter Wiring.
Analog outputs AO1-AO4 and AGND Available hardware for cabinet-specific setup only. Follow the cabinet documentation before connecting analog output control signals.
RS232 SER1_TXD/SER1_RXD/SGND; SER2_TXD/SER2_RXD/SER2_CTS/SER2_RTS/SGND Available hardware for cabinet-specific setup only. Follow the cabinet documentation before connecting serial instruments.
RS485 485_1A/485_1B/485_SGND and 485_2A/485_2B/485_SGND RS485 equipment such as energy meters and selected cabinet-specific sensors. RS485 energy metering and Mini Weather Station sensors.
M-Bus Not available on LX9 pro Not used. Use a model with M-Bus support if M-Bus is required.
1-Wire 1Wire, 1Wire-LED, and SGND Optional temperature measurement, for example soil temperature. 1-Wire options.
DC outputs DCOUT5-SGND and DCOUT-SGND 5 V, 12 V, or 24 V supply for supported external equipment. DC outputs.
Ethernet RJ45 Available hardware for cabinet-specific setup only. Follow the cabinet documentation before using Ethernet in FlexVander.

Optional standard features

Local push buttons

Local push buttons are optional physical inputs for local pump operation at the installation. Use FVALOCIN to select which digital input is used for the local push button.

Input Function Terminals Signal Condition
Input 1 Local push button DI1-GND S0/NPNNPN is a negative signal (minus).; JPDI1 = S. Program 1 only
Input 4 Local push button DI4-GND S0/NPNNPN is a negative signal (minus).; JPDI4 = S. DI4 not assigned to another function
Input 5 Local push button DI5-DCOUT PNPPNP is a positive signal (plus)./positive input referenced to GND; no JPDI jumper or S0 mode. Use a positive feed; GND is the input reference.

Pressure control

FlexVander LX9 pro can be installed with or without pressure control. If pressure control is used, connect the pressure transmitter to the relevant analog input and configure Pressure Control Settings.

AI1 is shown as Pressure line 1 in Emiko, and AI2 is shown as Pressure line 2 when separate pressure transmitters are used. Viking default for AI1-AI2 is 4-20 mA with JPAI1-JPAI2 installed. See Analog Transmitter Wiring for 4-20 mA and 0-10 V wiring principles.

Input Pressure line Terminals Signal
Input 1 Pressure line 1 AI1-AGND 4-20 mA transmitter; JPAI1 installed.
Input 2 Pressure line 2 AI2-AGND 4-20 mA transmitter; JPAI2 installed.

Before commissioning, verify the transmitter nameplate/datasheet and the selected input setup. Use AI2 only when separate pressure line 2 measurement is part of the solution.

RS485 energy metering

Use RS485 for energy meters when energy metering is part of the installation. Use Emiko-branded meters first where possible. See Energy Meters in Device Model for supported energy meters.

Node Meter for Condition
100 Submersible pump Use only when a submersible pump is installed.
101 Pressure pump 1 Use only when pressure pump 1 has its own meter.
102 Pressure pump 2 Use only when pressure pump 2 has its own meter.

RS485 terminals and termination

Port A B SGND
RS485 port 1 485_1A 485_1B 485_SGND
RS485 port 2 485_2A 485_2B 485_SGND

DC outputs

Use DC outputs only when the delivered installation assigns them to supported external equipment. Check the connected equipment nameplate and the delivered setup before using the outputs.

Output Terminals Rating Condition
5 V DC-Out DCOUT5-SGND 5 V / 300 mA Use only when included in the delivered setup.
12 V DC-Out DCOUT-SGND 12 V / 500 mA Use only when selected with JP101 and the supply is at least 14 VDC.
24 V DC-Out DCOUT-SGND 24 V / 250 mA Use only when selected with JP101 and the controller has AC supply.

Mini Weather Station sensors

DataGuard field sensors

Use DataGuard when Mini Weather Station values or other field values must be logged or shown in Emiko. FlexVander documents the physical input; DataGuard documents how the selected value is reported and logged.

See Climate and Level Sensors for serial instruments, Analog Inputs, Digital Inputs and Counters, and 1-Wire Temperature.

Additional analog inputs

The LX9 pro controller provides AI3 and AI4 for additional analog field sensors when the delivered setup assigns those inputs. The connected instrument nameplate or datasheet decides whether the input is configured for 4-20 mA or 0-10 V.

Input Terminals Signal Condition
Input 3 AI3-AGND 4-20 mA with JPAI3 installed; 0-10 V with JPAI3 not installed. Only when assigned by the delivered setup.
Input 4 AI4-AGND 4-20 mA with JPAI4 installed; 0-10 V with JPAI4 not installed. Only when assigned by the delivered setup.

Weather and field instruments

Use Instrument Families to select a supported serial instrument. Use the applicable Analog Inputs, Digital Inputs and Counters, or 1-Wire Temperature page for the other connection paths. If the instrument is not listed, use the cabinet documentation for the installed interface.

1-Wire options

Use 1-Wire for temperature measurement where the installation needs simple field temperature values, for example soil temperature. Configure the 1-Wire channel first, then add DataGuard reporting if the value must be logged or shown in Emiko.

Terminal Use Condition
1Wire 1-Wire bus Use with 1-Wire Temperature Monitoring
SGND Signal ground Required bus reference
1Wire-LED ID-Button LED output Not normally used for FlexVander field temperature sensors.

Hardware jumper reference

The Viking defaults are the delivered FlexVander setup. Change a jumper only when the connected signal or instrument requires a different input type.

Jumper Function Viking default Other setting Change when
JPDI1-JPDI4 DI1-DI4 as NPNNPN is a negative signal (minus)./S0-style inputs for local buttons and pump operating status. Position S = S0/NPNNPN is a negative signal (minus).-style input. Position N = PNPPNP is a positive signal (plus)./normal digital input. Change only when the connected digital signal is PNPPNP is a positive signal (plus)./normal positive input.
JPAI1-JPAI2 AI1-AI2 input type. Installed for 4-20 mA pressure transmitter use. Hardware range is 0-20 mA. Not installed = voltage input, 0-10 V. Change only when the transmitter nameplate/datasheet specifies 0-10 V voltage output.
JPAI3-JPAI4 AI3-AI4 input type for optional analog field sensors. Set by the delivered sensor setup. Installed = current input, 0-20 mA. Not installed = voltage input, 0-10 V. Change only when the connected instrument requires the other input type.
JPAO1-JPAO4 AO1-AO4 output type. Left as delivered unless analog outputs are part of the assisted setup. Position V = voltage output, 0-10 V. Position C = current output, 0-20 mA. Change only as part of an approved assisted setup.
TER1 RS485 port 1 endpoint termination. Installed = 120 ohm termination enabled. Not installed = termination disabled. Remove only when RS485 port 1 is not at a physical end of the bus.
TER2 RS485 port 2 endpoint termination. Installed = 120 ohm termination enabled. Not installed = termination disabled. Remove only when RS485 port 2 is not at a physical end of the bus.
JP101 DCOUT voltage. 24 V DC-Out Position 12V = 12 V / 500 mA. Position 24V = 24 V / 250 mA. Change only when the connected equipment nameplate/datasheet requires 12 V DC-Out.