Use this page as the terminal, wiring, jumper, and interface reference for a supported FlexVander DX4i PRO installation.
| Item | Value |
| Controller | DX4i PRO |
| Supply | 8-36 VDC |
| Outputs | 8 protected high-side digital outputs supplied from SUPP |
| Digital inputs | 8 inputs. DIN1-DIN4 can be normal digital inputs or S0 inputs. DIN5 can be wakeup input. |
| Analog inputs | 4 inputs, selectable 0-10 VDC or 0-20 mA |
| Field interfaces | RS485 port 1, shared RS485 port 2, 1-Wire, and 3.3 V DC output for supported accessories |
For basic FlexVander operation, connect supply, required pump command outputs, and required pump operating feedback signals for the selected program.
FVAPRG.FVALOCIN.FVADOUTT#.DWCONTACT# where the installation uses that option.| Supply | Connection | Terminal | Condition |
| 8-36 VDC | Positive | SUPP pin 28 or pin 29 |
Use both SUPP pins when output load requires it. |
| 8-36 VDC | Negative | PGND pin 27 |
Use as power supply return path. |
Program 1 controls one or two pressure pumps without a submersible pump. Wire the command outputs and feedback inputs for each installed pressure pump.
The outputs are high-side digital outputs, not potential-free relay contacts. Add interface relays when the pump panel requires dry contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-output behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
DOUT1 |
Start pressure pump 1 | Pin 30 | Required when pressure pump 1 is installed. |
DOUT2 |
Start pressure pump 2 | Pin 31 | Use only when pressure pump 2 is installed. |
DOUT3 |
Stop pressure pump 1 | Pin 32 | Required when pressure pump 1 is installed. |
DOUT4 |
Stop pressure pump 2 | Pin 33 | Use only when pressure pump 2 is installed. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DIN2 |
Pressure pump 1 | Pin 41, SGND |
Pump-running feedback | Required when pressure pump 1 is installed. |
DIN3 |
Pressure pump 2 | Pin 42, SGND |
Pump-running feedback | Use only when pressure pump 2 is installed. |
Program 2 controls one submersible pump and one or two pressure pumps. Wire command outputs and feedback inputs for each installed pump.
The outputs are high-side digital outputs, not potential-free relay contacts. Add interface relays when the pump panel requires dry contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-output behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
DOUT1 |
Start submersible pump | Pin 30 | Required when the submersible pump is installed. |
DOUT2 |
Start pressure pump 1 | Pin 31 | Required when pressure pump 1 is installed. |
DOUT3 |
Start pressure pump 2 | Pin 32 | Use only when pressure pump 2 is installed. |
DOUT4 |
Stop all pumps | Pin 33 | Required stop output for program 2. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DIN1 |
Submersible pump | Pin 40, SGND |
Pump-running feedback | Required when the submersible pump is installed. |
DIN2 |
Pressure pump 1 | Pin 41, SGND |
Pump-running feedback | Required when pressure pump 1 is installed. |
DIN3 |
Pressure pump 2 | Pin 42, SGND |
Pump-running feedback | Use only when pressure pump 2 is installed. |
| Interface | Terminals | Use | Continue |
| Digital inputs | DIN1-DIN8, SGND |
Pump feedback and local push buttons | Program 1, Program 2, Local push buttons |
| Digital outputs | DOUT1-DOUT8 |
Pump start and stop commands | Program 1, Program 2 |
| Analog inputs | AI1-AI4, AGND |
Pressure transmitters and analog field sensors | Pressure control, Mini Weather Station |
| RS485 | RS485_1+/RS485_1- and RS485_2+/RS485_2- |
Energy meters and supported field instruments | RS485 energy metering |
| 1-Wire | 1Wire pin 7, 1Wire-LED pin 8, SGND |
Supported temperature or ID accessories | Mini Weather Station |
Local push buttons are active only when the FlexVander setup uses FVALOCIN.
| Input | Function | Terminals | Signal | Condition |
DIN7 |
Program 1 pressure pump 1 button or program 2 pressure pump 1 button | Pin 46, SGND |
Local contact or input signal | Use only when selected by FVALOCIN. |
DIN8 |
Program 1 pressure pump 2 button or program 2 pressure pump 2 button | Pin 47, SGND |
Local contact or input signal | Use only when selected by FVALOCIN. |
DIN5 |
Program 2 submersible pump button | Pin 44, SGND |
Local contact or input signal | Use only when selected by FVALOCIN. |
Use pressure control only when pressure transmitters are installed. Select voltage or current input from the transmitter nameplate and the selected input setup.
| Input | Function | Terminals | Signal | Continue |
AI1 |
Pressure line 1 | Pin 17, AGND |
0-10 V or 0-20 mA | FVAPRESS, FVAPTRMODE |
AI2 |
Pressure line 2 | Pin 18, AGND |
0-10 V or 0-20 mA | FVAPRESSDELAY1/2 |
For transmitter wiring details, see Analog transmitter wiring.
Use RS485 energy metering only when an energy meter is installed and assigned to FlexVander. Terminate the RS485 bus only at the two physical endpoints.
| Port | Terminals | Use | Condition |
| RS485 port 1 | RS485_1+ pin 10, RS485_1- pin 11, SGND |
Energy meter bus | Use unless the cabinet documentation assigns port 2. |
| RS485 port 2 | RS485_2+ pin 13, RS485_2- pin 14, SGND |
Second RS485 bus | Use only when assigned. Port 2 shares resources with RS232 port 1. |
See Energy meters and Serial RS485 communication for the shared bus requirements.
Use the controller interfaces below only when the FlexVander installation includes matching sensors and DataGuard reporting.
| Sensor path | Interface | Terminals | Condition |
| Analog level or pressure sensor | Analog input | AI1-AI4, AGND |
Use only if the input is not already assigned to pump pressure control. |
| Temperature or ID accessory | 1-Wire | 1Wire pin 7, 1Wire-LED pin 8, SGND |
Use the accessory wiring supplied with the sensor. |
| Weather or level instrument | RS485 | RS485_1+, RS485_1-, SGND |
Use when the instrument is a supported RS485 device on the installation. |
See Climate and level sensors for supported serial instruments.
| Output | Terminals | Use | Condition |
| 3.3 V DC output | DC-OUT pin 3 and SGND pin 5 on connector X1 |
Supported low-voltage accessories | This is not a 24 V transmitter supply. |
The Viking defaults are the delivered FlexVander setup. Change a jumper only when the connected signal or instrument requires a different input type.
| Jumper | Function | Viking default | Other setting | Change when |
JP8-JP11 |
Input mode for DIN1-DIN4 |
Position 1-2 for standard FlexVander contact/S0-style wiring | Position 2-3 for normal positive digital input | The connected feedback or push-button signal requires normal input mode. |
JP1, JP14, JP16, JP17 |
Analog input mode | Current input when pressure transmitter is delivered | Voltage input | The connected transmitter is 0-10 V. |
JP7, JP12 |
RS485 termination | Not installed unless delivered as an RS485 endpoint | Installed | The controller is one of the two physical endpoints on the RS485 bus. |