Use this page as the terminal, wiring, jumper, and interface reference for a supported FlexVander NX 910 installation.
| Item | Value |
| Controller | NX 910 |
| Supply | 100-260 VAC and 8-36 VDC |
| Outputs | 4 normally-open relay outputs, max. 5 A @ 250 VAC / 30 VDC |
| Digital inputs | 5 inputs. DIN1-DIN4 can be normal digital inputs or S0 inputs. DIN5 can be wakeup input. |
| Analog inputs | 2 inputs, selectable 0-10 VDC or 0-20 mA |
| Field interfaces | RS485, 1-Wire, and selectable external DC output for supported sensors and accessories |
For basic FlexVander operation, connect supply, required pump command outputs, and required pump operating feedback signals for the selected program.
FVAPRG.FVALOCIN.FVADOUTT#.DWCONTACT# where the installation uses that option.| Supply | Connection | Terminal | Condition |
| 100-260 VAC | Phase | P |
Use for AC supply. |
| 100-260 VAC | Neutral | N |
Use for AC supply. |
| 100-260 VAC | Protective earth | PE terminal | Required with AC supply. |
| 8-36 VDC | Positive | DCIN |
Use for DC supply. |
| 8-36 VDC | Negative | XGND |
AC and DC supply can be connected at the same time when required by the cabinet design. |
Program 1 controls one or two pressure pumps without a submersible pump. Wire the command outputs and feedback inputs for each installed pressure pump.
The relay outputs are potential-free normally-open contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-contact behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
| Relay 1 | Start pressure pump 1 | R1A, R1B |
Required when pressure pump 1 is installed. |
| Relay 2 | Start pressure pump 2 | R2A, R2B |
Use only when pressure pump 2 is installed. |
| Relay 3 | Stop pressure pump 1 | R3A, R3B |
Required when pressure pump 1 is installed. |
| Relay 4 | Stop pressure pump 2 | R4A, R4B |
Use only when pressure pump 2 is installed. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DI2 |
Pressure pump 1 | DI2, GND |
Pump-running feedback | Required when pressure pump 1 is installed. |
DI3 |
Pressure pump 2 | DI3, GND |
Pump-running feedback | Use only when pressure pump 2 is installed. |
Program 2 controls one submersible pump and one or two pressure pumps. Wire command outputs and feedback inputs for each installed pump.
The relay outputs are potential-free normally-open contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-contact behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
| Relay 1 | Start submersible pump | R1A, R1B |
Required when the submersible pump is installed. |
| Relay 2 | Start pressure pump 1 | R2A, R2B |
Required when pressure pump 1 is installed. |
| Relay 3 | Start pressure pump 2 | R3A, R3B |
Use only when pressure pump 2 is installed. |
| Relay 4 | Stop all pumps | R4A, R4B |
Required stop output for program 2. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DI1 |
Submersible pump | DI1, GND |
Pump-running feedback | Required when the submersible pump is installed. |
DI2 |
Pressure pump 1 | DI2, GND |
Pump-running feedback | Required when pressure pump 1 is installed. |
DI3 |
Pressure pump 2 | DI3, GND |
Pump-running feedback | Use only when pressure pump 2 is installed. |
| Interface | Terminals | Use | Continue |
| Digital inputs | DI1-DI5, GND |
Pump feedback and local push buttons | Program 1, Program 2, Local push buttons |
| Relay outputs | R1A-R4B |
Pump start and stop commands | Program 1, Program 2 |
| Analog inputs | AI1, AI2, AGND |
Pressure transmitters and analog field sensors | Pressure control, Mini Weather Station |
| RS485 | RS485_1+, RS485_1-, SGND |
Energy meters and supported field instruments | RS485 energy metering |
| 1-Wire | 1Wire, 1Wire-LED, SGND |
Supported temperature or ID accessories | Mini Weather Station |
Local push buttons are active only when the FlexVander setup uses FVALOCIN. Set the input jumper to match the installed signal type.
| Input | Function | Terminals | Signal | Condition |
DI1 |
Program 1 pressure pump 1 button | DI1, GND |
Local contact or input signal | Use only when selected by FVALOCIN. |
DI4 |
Program 1 pressure pump 2 button or program 2 local button | DI4, GND |
Local contact or input signal | Use only when selected by FVALOCIN. |
Use pressure control only when pressure transmitters are installed. Select voltage or current input from the transmitter nameplate and the selected input setup.
| Input | Function | Terminals | Signal | Continue |
AI1 |
Pressure line 1 | AI1, AGND |
0-10 V or 0-20 mA | FVAPRESS, FVAPTRMODE |
AI2 |
Pressure line 2 | AI2, AGND |
0-10 V or 0-20 mA | FVAPRESSDELAY1/2 |
For transmitter wiring details, see Analog transmitter wiring.
Use RS485 energy metering only when an energy meter is installed and assigned to FlexVander. Terminate the RS485 bus only at the two physical endpoints.
| Port | Terminals | Use | Condition |
| RS485 port 1 | RS485_1+, RS485_1-, SGND |
Energy meter bus | Use a twisted pair and common signal ground. |
See Energy meters and Serial RS485 communication for the shared bus requirements.
Use the controller interfaces below only when the FlexVander installation includes matching sensors and DataGuard reporting.
| Sensor path | Interface | Terminals | Condition |
| Analog level or pressure sensor | Analog input | AI1 / AI2, AGND |
Use only if the input is not already assigned to pump pressure control. |
| Temperature or ID accessory | 1-Wire | 1Wire, 1Wire-LED, SGND |
Use the accessory wiring supplied with the sensor. |
| Weather or level instrument | RS485 | RS485_1+, RS485_1-, SGND |
Use when the instrument is a supported RS485 device on the installation. |
See Climate and level sensors for supported serial instruments.
| Output | Terminals | Use | Condition |
| 12 V / 24 V DC output | DCOUT, SGND |
Supported sensors and accessories | Select the voltage that matches the installed load and current limit. |
The Viking defaults are the delivered FlexVander setup. Change a jumper only when the connected signal or instrument requires a different input type.
| Jumper | Function | Viking default | Other setting | Change when |
JPDI1-JPDI4 |
Input mode for DI1-DI4 |
Position S for standard FlexVander contact/S0-style wiring |
Position N for normal positive digital input |
The connected feedback or push-button signal requires normal input mode. |
JPAI1-JPAI2 |
Analog input mode | Current input when pressure transmitter is delivered | Voltage input | The connected transmitter is 0-10 V. |
| RS485 termination | 120 ohm endpoint termination | Installed only when delivered as an RS485 endpoint | Not installed | The controller is not one of the two physical endpoints on the RS485 bus. |
| DC output selection | 12 V or 24 V accessory supply | 24 V when delivered for standard sensor supply | 12 V | The connected sensor requires 12 V and stays within the current rating. |