Use this page as the terminal, wiring, jumper, and interface reference for a supported FlexVander AX9 ENCORE installation.
| Item | Value |
| Controller | AX9 ENCORE |
| Supply | 100-260 VAC and 8-36 VDC |
| Outputs | 4 normally-open relay outputs, max. 5 A @ 250 VAC / 30 VDC |
| Digital inputs | 5 inputs. DIN1-DIN4 can be normal digital inputs or S0 inputs. DIN5 can be wakeup input. |
| Analog inputs | 2 inputs, selectable 0-10 VDC or 0-20 mA |
| Field interfaces | 1-Wire, 24 V DC output, and on-demand RS485 port 2 when available in the installed controller |
For basic FlexVander operation, connect supply, required pump command outputs, and required pump operating feedback signals for the selected program.
FVAPRG.FVALOCIN.FVADOUTT#.DWCONTACT# where the installation uses that option.| Supply | Connection | Terminal | Condition |
| 100-260 VAC | Phase | P |
Use for AC supply. |
| 100-260 VAC | Neutral | N |
Use for AC supply. |
| 100-260 VAC | Protective earth | PE terminal | Required with AC supply. |
| 8-36 VDC | Positive | DCIN |
Use for DC supply. |
| 8-36 VDC | Negative | XGND |
AC and DC supply can be connected at the same time when required by the cabinet design. |
Program 1 controls one or two pressure pumps without a submersible pump. Wire the command outputs and feedback inputs for each installed pressure pump.
The relay outputs are potential-free normally-open contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-contact behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
| Relay 1 | Start pressure pump 1 | R1A, R1B |
Required when pressure pump 1 is installed. |
| Relay 2 | Start pressure pump 2 | R2A, R2B |
Use only when pressure pump 2 is installed. |
| Relay 3 | Stop pressure pump 1 | R3A, R3B |
Required when pressure pump 1 is installed. |
| Relay 4 | Stop pressure pump 2 | R4A, R4B |
Use only when pressure pump 2 is installed. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DI2 |
Pressure pump 1 | DI2, signal ground |
Pump-running feedback | Required when pressure pump 1 is installed. |
DI3 |
Pressure pump 2 | DI3, signal ground |
Pump-running feedback | Use only when pressure pump 2 is installed. |
Program 2 controls one submersible pump and one or two pressure pumps. Wire command outputs and feedback inputs for each installed pump.
The relay outputs are potential-free normally-open contacts. FVADOUTT# sets pulse time. DWCONTACT# can change stop-contact behaviour where the installation requires it.
| Output | Function | Terminals | Condition |
| Relay 1 | Start submersible pump | R1A, R1B |
Required when the submersible pump is installed. |
| Relay 2 | Start pressure pump 1 | R2A, R2B |
Required when pressure pump 1 is installed. |
| Relay 3 | Start pressure pump 2 | R3A, R3B |
Use only when pressure pump 2 is installed. |
| Relay 4 | Stop all pumps | R4A, R4B |
Required stop output for program 2. |
Connect a compatible pump-running or status signal to each listed input. The signal must be active when the pump is running.
| Input | Pump | Terminals | Signal | Condition |
DI1 |
Submersible pump | DI1, signal ground |
Pump-running feedback | Required when the submersible pump is installed. |
DI2 |
Pressure pump 1 | DI2, signal ground |
Pump-running feedback | Required when pressure pump 1 is installed. |
DI3 |
Pressure pump 2 | DI3, signal ground |
Pump-running feedback | Use only when pressure pump 2 is installed. |
| Interface | Terminals | Use | Continue |
| Digital inputs | DI1-DI5, signal ground |
Pump feedback and local push buttons | Program 1, Program 2, Local push buttons |
| Relay outputs | R1A-R4B |
Pump start and stop commands | Program 1, Program 2 |
| Analog inputs | AI1, AI2, AGND |
Pressure transmitters and analog field sensors | Pressure control, Mini Weather Station |
| On-demand RS485 | RS485_2+, RS485_2-, SGND |
Energy meters and supported field instruments | RS485 energy metering |
| 1-Wire | 1Wire, 1Wire-LED, SGND |
Supported temperature or ID accessories | Mini Weather Station |
Local push buttons are active only when the FlexVander setup uses FVALOCIN. Set the input jumper to match the installed signal type.
| Input | Function | Terminals | Signal | Condition |
DI1 |
Program 1 pressure pump 1 button | DI1, signal ground |
Local contact or input signal | Use only when selected by FVALOCIN. |
DI4 |
Program 1 pressure pump 2 button or program 2 local button | DI4, signal ground |
Local contact or input signal | Use only when selected by FVALOCIN. |
Use pressure control only when pressure transmitters are installed. Select voltage or current input from the transmitter nameplate and the selected input setup.
| Input | Function | Terminals | Signal | Continue |
AI1 |
Pressure line 1 | AI1, AGND |
0-10 V or 0-20 mA | FVAPRESS, FVAPTRMODE |
AI2 |
Pressure line 2 | AI2, AGND |
0-10 V or 0-20 mA | FVAPRESSDELAY1/2 |
For transmitter wiring details, see Analog transmitter wiring.
Use RS485 energy metering only when the installed AX9 ENCORE has the on-demand RS485 option enabled and assigned. Terminate the RS485 bus only at the two physical endpoints.
| Port | Terminals | Use | Condition |
| RS485 port 2 | RS485_2+, RS485_2-, SGND |
Energy meter bus | Use only when the on-demand RS485 option is enabled and assigned. |
See Energy meters and Serial RS485 communication for the shared bus requirements.
Use the controller interfaces below only when the FlexVander installation includes matching sensors and DataGuard reporting.
| Sensor path | Interface | Terminals | Condition |
| Analog level or pressure sensor | Analog input | AI1 / AI2, AGND |
Use only if the input is not already assigned to pump pressure control. |
| Temperature or ID accessory | 1-Wire | 1Wire, 1Wire-LED, SGND |
Use the accessory wiring supplied with the sensor. |
| Weather or level instrument | On-demand RS485 | RS485_2+, RS485_2-, SGND |
Use only when the RS485 option is enabled and assigned. |
See Climate and level sensors for supported serial instruments.
| Output | Terminals | Use | Condition |
| 24 V DC output, max. 250 mA | DCOUT, GND |
Supported sensors and accessories | The 24 V output requires AC supply to be present. |
The Viking defaults are the delivered FlexVander setup. Change a jumper only when the connected signal or instrument requires a different input type.
| Jumper | Function | Viking default | Other setting | Change when |
JPDI1-JPDI4 |
Input mode for DI1-DI4 |
Position S for standard FlexVander contact/S0-style wiring |
Position N for normal positive digital input |
The connected feedback or push-button signal requires normal input mode. |
JPAI1-JPAI2 |
Analog input mode | Current input when pressure transmitter is delivered | Voltage input | The connected transmitter is 0-10 V. |
TER2 |
RS485 port 2 termination | Not installed unless delivered as an RS485 endpoint | Installed | The controller is one of the two physical endpoints on the RS485 bus. |
Public revision 21/08/2026