Use this page when the installation includes pressure control with a pressure transmitter. Correct pressure setup makes the operating pressure visible in Emiko and allows FlexVander to stop and alarm when the configured pressure conditions are not met.
Pressure line 1 or Pressure line 2 when the pressure transmitter, pressure settings, and reporting setup are correct.FlexVander uses the analog inputs as pressure lines when pressure control is enabled.
AI1 is shown as Pressure line 1 in Emiko and uses parameter index #1.AI2 is shown as Pressure line 2 in Emiko and uses parameter index #2.Use these commands to restore pressure circuit settings for a selected pressure line.
FVAPRESSFAC1 restores pressure line 1 / AI1.FVAPRESSFAC2 restores pressure line 2 / AI2.FVAFAC for FlexVander product setup and shared controller settings.| Command | Function |
FVAPRESSFAC1 |
Restores pressure line 1 / AI1 to FlexVander pressure circuit factory settings. |
FVAPRESSFAC2 |
Restores pressure line 2 / AI2 to FlexVander pressure circuit factory settings. |
Use this sequence when a pressure transmitter has been installed and the pressure value must be used by FlexVander and shown in Emiko.
VRTYPE# for the electrical signal type.TMIN# and TMAX# for the transmitter range.FVAPRESS and FVAPTRMODE.VRMIN#, VRMAX#, and VRHYS#.FVAPRESSDELAY1 or FVAPRESSDELAY2 for how long pressure may take to become valid after pump start.The selected pump program and transmitter layout decide which analog input, Emiko pressure name, and parameter index to use.
| Selected program | Transmitter layout | Analog input | Emiko pressure name | Used for |
| Program 1 | Shared transmitter | AI1parameter index #1 |
Pressure line 1 |
Pressure pump 1 and/or pressure pump 2 on the same pressure system. |
| Program 1 | Separate transmitters | AI1parameter index #1AI2parameter index #2
|
Pressure line 1Pressure line 2
|
AI1 for pressure pump 1. AI2 for pressure pump 2. |
| Program 2 | Shared transmitter | AI1parameter index #1 |
Pressure line 1 |
Shared pressure value for the submersible pump and the selected pressure pump(s). |
For 4-20 mA and 0-10 V wiring principles, see Analog Transmitter Wiring.
Set the analog input signal type before scaling the transmitter.
AI1 and AI2 is normally 4-20 mA with the analog input jumper installed.| Parameter | Index | Range | Format | Default | Example |
VRTYPE# |
1..32 | 0..5 |
0 = 4-20 mA 1 = 0-5 V 2 = 0-10 V 3 = 0-20 mA 4 = 0-30 V 5 = 0-30 V > 0-10 V |
0 | VRTYPE1 2 |
|
Choose the value that matches the installed input hardware and transmitter wiring. For NRG 200M selector |
|||||
Configure which pumps must be activated for pressure control.
| Parameter | Index | Range | Format | Default | Example |
FVAPRESS |
- | 0..3 |
0 = Disabled FlexVander program 1 without submersible pump 1 = Pressure pump 1 2 = Pressure pump 2 3 = Pressure pump 1 and 2 FlexVander program 2 with submersible pump 1 = Submersible pump and pressure pump 1 and 2 |
0 | FVAPRESS 1 |
When FVAPRESS is changed from 0 to 1, 2, or 3, FlexVander fills missing pressure control and pressure publish/reporting defaults. Existing nonzero tuned values are kept, except a generic periodic VRLOGMODE# 1 is changed to the FlexVander reporting default 4.
Changing FVAPRESS between enabled pressure modes 1, 2, and 3 preserves already tuned pressure parameters.
Set whether the pressure transmitter must be shared or whether each pressure pump has its own pressure transmitter.
| Parameter | Index | Range | Format | Default | Example |
FVAPTRMODE |
- | 1..2 |
FlexVander program 1 without submersible pump 1 = Shared 2 = Separate FlexVander program 2 with submersible pump 1 = Shared |
1 | FVAPTRMODE 1 |
TMIN# and TMAX# define the transmitter measuring range. They are not pressure alarm limits.
0..10 bar transmitter, use TMIN# 0 and TMAX# 10.0..16 bar transmitter, use TMIN# 0 and TMAX# 16.| Parameter | Index | Range | Format | Default | Example |
TMIN# |
1..32 | -32768..32767 | Engineering value | 0 | TMIN1 10 |
For selector-specific DataGuard paths, follow the selector rule. With VRDATATYPE#=9013, TMIN# is the lower post-input signal range in mV for the RNRG/NRG 200P wind vane; for example, use TMIN1=0 with TMAX1=5000 for a real 0..5 V signal. See 9013 setup examples. With analog VRDATATYPE#=9007, it is the lower radar distance-to-water range in metres. |
|||||
| Parameter | Index | Range | Format | Default | Example |
TMAX# |
1..2 | -2147483647..2147483647 | Engineering value | 16 | TMAX1 16 |
Pressure limits define when the scaled pressure value is too low or too high. Hysteresis prevents repeated status changes when the pressure is close to a limit.
VRMIN# for the low pressure limit.VRMAX# for the high pressure limit.VRHYS# for pressure limit hysteresis.VRMIN1 60 means 6.0 bar.For how missing pressure values are filled when pressure control is enabled, see FVAPRESS.
Example: for a 0-16 bar pressure transmitter, TMIN1 0 and TMAX1 16 define the transmitter range. A typical operating setup can be VRMIN1 60 for 6.0 bar, VRMAX1 100 for 10.0 bar, and VRHYS1 5 for 0.5 bar hysteresis.
The actual values must match the pump, pipe system, and irrigation requirement.
With this setup, high pressure status is entered when the pressure is at or above 10.0 bar. After high status is active, it is not released until the pressure is at or below 9.5 bar (VRMAX1 - VRHYS1).
Low pressure status is entered when the pressure is at or below 6.0 bar. After low status is active, it is not released until the pressure is at or above 6.5 bar (VRMIN1 + VRHYS1).
Status transitions are filtered by VRFIL#. Brief spikes should therefore not be treated as immediate final status changes. FlexVander uses the resulting pressure status for pressure control, stop/alarm behaviour, and start blocking according to the selected program and setup.
| Parameter | Index | Range | Format | Default | Example |
VRMIN# |
1..2 | -2147483647..2147483647 | Engineering value multiplied by 10 | 60 | VRMIN1 60 |
VRMAX# |
1..2 | -2147483647..2147483647 | Engineering value multiplied by 10 | 100 | VRMAX1 100 |
VRHYS# |
1..2 | 0..32767 | Engineering value multiplied by 10 | 5 | VRHYS1 5 |
| Parameter | Index | Range | Format | Default | Example |
VRMAX# |
1..2 | -2147483647..2147483647 | Engineering value multiplied by 10 | 100 | VRMAX1 100 |
| Parameter | Index | Range | Format | Default | Example |
VRHYS# |
1..2 | 0..32767 | Engineering value multiplied by 10 | 5 | VRHYS1 5 |
Set the time from pump start until valid operating pressure must be reached.
| Parameter | Index | Range | Format | Default | Example |
FVAPRESSDELAY# |
1..2 | 0..30 | Number of minutes | 8 | FVAPRESSDELAY1 10 |
These settings are special-case tuning values for signal direction, scaling boundaries, filtering, spike handling, and damping. Change them only for noisy pressure signals, special scaling cases, or support-guided tuning.
For how missing pressure-control values are filled when pressure control is enabled, see FVAPRESS. For full analog parameter behaviour, see the shared analog input settings.
| Parameter | Index | Range | Format | Default | Example |
VRSWAP# |
1..2 | 0..1 | 0 = Normal signal direction 1 = Swapped signal direction. Use only if the measured pressure moves opposite of expected. |
0 | VRSWAP1 0 |
VRPRO# |
1..2 | -2147483647..2147483647 | Support-guided profile/reference value | 0 | VRPRO1 0 |
VRFIL# |
1..2 | 0..127 | Filter/confirmation time in seconds before status changes are accepted | 2 | VRFIL1 2 |
VRSPIKES# |
1..2 | 0..100 | Spike rejection size as percent of measurement range | 10 | VRSPIKES1 10 |
VRSPIKET# |
1..2 | 0..30000 | Spike rejection time in milliseconds | 200 | VRSPIKET1 200 |
VRDMPV# |
1..2 | 0..1000 | Damping value for unstable pressure readings. Percent of measurement range multiplied by 10. | 800 | VRDMPV1 800 |
VRDMPT# |
1..2 | 0..10000 | Damping time in milliseconds for unstable pressure readings | 100 | VRDMPT1 100 |
| Parameter | Index | Range | Format | Default | Example |
VRPRO# |
1..2 | -2147483647..2147483647 | Support-guided profile/reference value | 0 | VRPRO1 0 |
| Parameter | Index | Range | Format | Default | Example |
VRFIL# |
1..2 | 0..127 | Filter/confirmation time in seconds before status changes are accepted | 2 | VRFIL1 2 |
| Parameter | Index | Range | Format | Default | Example |
VRSPIKES# |
1..2 | 0..100 | Spike rejection size as percent of measurement range | 10 | VRSPIKES1 10 |
| Parameter | Index | Range | Format | Default | Example |
VRSPIKET# |
1..2 | 0..30000 | Spike rejection time in milliseconds | 200 | VRSPIKET1 200 |
| Parameter | Index | Range | Format | Default | Example |
VRDMPV# |
1..2 | 0..1000 | Damping value for unstable pressure readings. Percent of measurement range multiplied by 10. | 800 | VRDMPV1 800 |
| Parameter | Index | Range | Format | Default | Example |
VRDMPT# |
1..2 | 0..10000 | Damping time in milliseconds for unstable pressure readings | 100 | VRDMPT1 100 |
These settings allow FlexVander pressure line values to be reported and shown in Emiko when reporting is part of the solution.
For how missing reporting values are filled when pressure control is enabled, see FVAPRESS. Leave these settings at the FlexVander defaults unless support or a reporting requirement needs a change.
For the complete DataGuard analog workflow, see DataGuard via Analog Inputs. For analog source setup, see the shared analog input settings.
| Parameter | Index | Range | Format | Default | Example |
VREQT# |
1..2 | 0..35 | Equipment type for the value in Emiko. 16 = FlexVander. |
16 | VREQT1 16 |
VRDATATYPE# |
1..2 | 0..1312 | Data type for the value sent to Emiko. 1102 = Pressure. |
1102 | VRDATATYPE1 1102 |
VRLOGMODE# |
1..2 | 0..4 | 0 = Disabled 1 = Periodic 4 = Hybrid reporting with periodic updates and event/threshold updates |
4 | VRLOGMODE1 4 |
VRLOGINT# |
1..2 | 0..31 | 19 = Every 4 hours |
19 | VRLOGINT1 19 |
VRLOGHYS# |
1..2 | 0..32767 | Threshold/hysteresis used for reporting changes | 5 | VRLOGHYS1 5 |
| Parameter | Index | Range | Format | Default | Example |
VRDATATYPE# |
1..2 | 0..1312 | Data type for the value sent to Emiko. 1102 = Pressure. |
1102 | VRDATATYPE1 1102 |
| Parameter | Index | Range | Format | Default | Example |
VRLOGMODE# |
1..2 | 0..4 | 0 = Disabled 1 = Periodic 4 = Hybrid reporting with periodic updates and event/threshold updates |
4 | VRLOGMODE1 4 |
| Parameter | Index | Range | Format | Default | Example |
VRLOGINT# |
1..2 | 0..31 | 19 = Every 4 hours |
19 | VRLOGINT1 19 |
| Parameter | Index | Range | Format | Default | Example |
VRLOGHYS# |
1..2 | 0..32767 | Threshold/hysteresis used for reporting changes | 5 | VRLOGHYS1 5 |
After wiring and pressure setup, start the relevant pump and confirm that the live pressure value is shown in Emiko as the expected pressure line before handover.
If pressure is not shown, verify the signal type, transmitter scaling, pressure enable settings, and Emiko reporting setup.
Extra non-pressure sensor values are handled on the relevant sensor setup pages.
Public revision 21/08/2026