FlexVander program settings

Use this page to configure the local FlexVander pump program and the controller behaviour that supports Emiko operation, optional SMS or voice workflows, and local push-button operation.

Recommended commissioning order

  1. Load FlexVander factory settings.
  2. Select the required pump program.
  3. Configure messages, timers, and any optional local operation inputs.
  4. Verify operation in Emiko before handing the installation over for daily use.

Basic settings

Basic settings define the pump layout and controller behaviour used by Emiko, local/offline operation methods, and the installed input/output wiring.

Factory settings

Use this only before first commissioning or after support has approved a return to the FlexVander baseline. Record any site values that must be entered again.

Command Function
FVAFAC Loads FlexVander factory settings for product setup and shared controller settings used by FlexVander.

ProgramProgram type installed in the device.

Set which program, and therefore how many pumps, the equipment must control.

Parameter Index Range Format Default Example
FVAPRG - 0..48

0 = Disabled

FlexVander program 1 without submersible pumpFlexVander program 1 controls pressure pumps without a submersible pump.

1 = Pressure pump 1

2 = Pressure pump 2

3 = Pressure pump 1 and 2

FlexVander program 2 with submersible pumpFlexVander program 2 controls pressure pumps with a shared submersible pump.

16 = Submersible pump and pressure pump 1

32 = Submersible pump and pressure pump 2

48 = Submersible pump and pressure pump 1 and 2

0 FVAPRG 1

Operating messages

Select which normal operating messages the system must send to the person who started the pump and to the configured operating-message recipients.

Parameter Index Range Format Default Example
FVAOPMSG - 0..31

0 = Disabled

1 = Send when pressure pump starts

2 = Send when pressure pump stops

4 = Send when the desired operating pressure is reached (requires pressure control)

8 = Send when submersible pump starts

16 = Send when submersible pump stops

22 FVAOPMSG 31

Name

Set the unit name, which is used for example together with messagesMessage sent by the equipment to one or more configured users, for example an SMS or email alarm.. The irrigation system name is typically used.

Parameter Index Range Format Default Example
NAME - 1..50 characters Text string Viking NAME Tinnetvej 70

Timer

Timer settings.

Operating signal monitoring

Set the time from when the pressure pump starts until the expected operating signal must be detected.

Parameter Index Range Format Default Example
FVAOPDELAY - 0..3600 Number of seconds 5 FVAOPDELAY 10

Pulse time

FVADOUTT# sets how long the start output may stay active after FlexVander has requested a pump start. The required value depends on how the pump control circuit is built.

Parameter Index Range Format Default Example
FVADOUTT# 1..4 0..3600 Number of seconds 2 FVADOUTT1 300

Fill time

FVASUBFILL is used only when Program 2 is active with a submersible pump. Set the time from submersible pump start until the pressure pump may start.

Parameter Index Range Format Default Example
FVASUBFILL - 0..3600 Number of seconds 120 FVASUBFILL 180

Digital inputs/outputs

Use these settings only for the installed input/output functions that are part of the FlexVander installation.

Operation input

Set which digital input must be used if an operating push button is installed. The button is used for manual operation of the pumps.

Parameter Index Range Format Default Example
FVALOCIN - 0..8

0 = Disabled

1 = Digital input 1

2 = Digital input 2

3 = Digital input 3

4 = Digital input 4

5 = Digital input 5

6 = Digital input 6

7 = Digital input 7

8 = Digital input 8

0 FVALOCIN 4

Output type

Set whether the output must be NONormally open. or NCNormally closed..

Parameter Index Range Format Default Example
DWCONTACT# 1..28 0..1

0 = Normally open (NO)

1 = Normally closed (NC)

0 DWCONTACT1 1

Advanced settings

These settings normally stay at the FlexVander defaults. Change them only when the installation or support case requires it.

Digital output mode

DWTYPE# controls how each digital output behaves. Leave the FlexVander default at 1 unless the installation or support case explicitly requires another value. A wrong value can break the FlexVander output function, especially when the matching DWCONTACT# output contact type has been changed to NCNormally closed..

Parameter Index Range Format Default Example
DWTYPE# 1..28 0..2

0 = Pulse output, minimum 500 ms

1 = On/off

2 = On/off, and status is retained after restart

1 DWTYPE1 2

Digital input counter mode

TIN1..3 support FlexVander digital input hour/counter handling. Leave them at 2 when input hour counters are required.

When TIN# is changed to 1 for high-speed counter use, runtime applies the binding. Keep TIN# 2 where only input timer behavior is needed.

Parameter

Index Range Format Default Example
TIN# 1..16 0..2

0 = Disabled

1 = Use VRC and VRCT

2 = Use VRCT only

0 TIN1 2

Voice control

VOICE controls local voice-call operation. The FlexVander default is 2 and should normally be left unchanged.

Parameter Index Range Format Default Example
VOICE - 0..4

0 = Disabled

1 = FlexGuard

2 = FlexVander

3 = Not used

4 = ProPower equipment

- VOICE 2

Input debounce time

DRT1..4 are input debounce or confirmation timers. When a value is set, the input signal must remain active for the configured time before FlexVander accepts the input state. The default is 0.

Change this only if unstable signals, short false pulses, or contact bounce create problems.

Parameter Index Range Format Default Example
DRT# 1..28 0..127 Number of seconds 0 DRT1 2

Advanced settings for supported installed models

GSMGSM (Global System for Mobile Communications) is a widely used standard for mobile communication and data. antenna

GSMANT is used only on installed models with selectable internal or external antenna hardware. Compatibility: VikMote AX9 turbo and VikMote AX9 encore only.

Do not use this setting unless the installed hardware explicitly supports the selectable antenna function.

Parameter Index Range Format Default Example
GSMANT 1 0..1

0 = Internal GSM antenna

1 = External GSM antenna connector

Note: Internal/external switching is available only on AX9 turbo and AX9 encore. On other supported controllers, runtime keeps external antenna mode.

- GSMANT 1

Related setup