Description WAS DN80-1-2 SEP /B TIN WAS DN80-1-2 SA /B TIN WAS DN80-2-2 SA /B TIN WAS DN80-3-2 SA /B TIN
Item number 1006019
Series

TIN

TIN

TIN

TIN

Model

Well

Well

Well

Well

Application Drinking water Drinking water Drinking water Drinking water
Installation

Below-ground installation

Below-ground installation

Below-ground installation

Below-ground installation

Power connection

Connected to ServicePedestal

230VAC / 10A

230VAC / 10A

230VAC / 10A

Control box connections

1

1

2

3

Water inlet 1 x OD 110 mm PEHD SDR17 pipe 1 x OD 110 mm PEHD SDR17 pipe 1 x OD 110 mm PEHD SDR17 pipe

1 x OD 110 mm PEHD SDR17 pipe

Water outlet

1 x OD 90 mm PEHD SDR17 pipe

1 x OD 90 mm PEHD SDR17 pipe 2 x OD 90 mm PEHD SDR17 pipe

3 x OD 90 mm PEHD SDR17 pipe

Built-in GSM controller/data logger/control

-

yes

yes

yes

Monitoring of water temperature - Option Option Option
Monitoring of temperature in the well - Option Option Option
Monitoring of water in the sump/base - Option Option Option

Watertight

yes

yes

yes

yes

Uplift resistant with water up to ground level

yes

yes

yes

yes

Steel-reinforced double bottom

yes

yes

yes

yes

Lifting eyes

2

2

2

2

Flow meter - Manufacturer

Kamstrup

Kamstrup

Kamstrup

Kamstrup

Flow meter - Battery life Up to 16 years Up to 16 years Up to 16 years Up to 16 years
Flow meter - Replaceable battery No No No No

Flow meter - Flow Q1

0,394 m3/h

0,394 m3/h

0,394 m3/h

0,394 m3/h

Flow meter - Flow Q3

63 m3/h

63 m3/h

63 m3/h

63 m3/h

Flow meter - Class R315 R315 R315 R315

Flow meter - Approval

MID

MID

MID

MID

Flow meter - Communication

M-Bus

M-Bus

M-Bus

M-Bus

Valve - Seal EPDM EPDM EPDM EPDM

Valve - Opening time

10 seconds

10 seconds

10 seconds

10 seconds

Valve - Closing time

20 seconds

20 seconds

20 seconds

20 seconds

Valve - Function NC

Option

Option

Option

Option

TBS - Category if installed

4

4

4

4

Internal technical insulation of pipes/equipment - - - -
Water temperature 0.1-50 deg C 0.1-50 deg C 0.1-50 deg C 0.1-50 deg C

Internal temperature

2-55 deg C

2-55 deg C

2-55 deg C

2-55 deg C

External temperature (below ground)

0-20 deg C

0-20 deg C

0-20 deg C

0-20 deg C

Flanged PN

25

25

25

25

Thermostatically controlled heater

-

-

-

-

Cable entry seals for power cables

yes

yes

yes

yes

Bottom sump for possible condensate collection

yes

yes

yes

yes

Material

SPS double wall SN4

SPS double wall SN4

SPS double wall SN4

SPS double wall SN4

Top finish

Concrete ring/well frame or aluminium cover

Concrete ring/well frame or aluminium cover

Concrete ring/well frame or aluminium cover

Concrete ring/well frame or aluminium cover

Heavy traffic

Concrete ring must be installed

Concrete ring must be installed

Concrete ring must be installed

Concrete ring must be installed

Weight

-

-

-

-

External dimensions (HxWxD)

-

-

-

-

Base plate dimensions

2000x1700 mm

2000x1700 mm

2000x1700 mm

2000x1700 mm

External height

2300 mm

2300 mm

2300 mm

2300 mm

Internal diameter

dia. 1250 mm

dia. 1250 mm

dia. 1250 mm

dia. 1250 mm

Riser height

350 mm

350 mm

350 mm

350 mm

Internal riser diameter

dia. 600 mm

dia. 600 mm

dia. 600 mm

dia. 600 mm

Total external height

2650 mm

2650 mm

2650 mm

2650 mm