Configuration

These settings are normally handled during commissioning or service.

Use this page to enable vNet and to enable only the fixed module positions that are physically installed in the system.

Enable vNet

Use VNMON to enable or disable the shared vNet runtime.

Parameter Index Range Format Default Example
VNMON - 0..1

0 = vNet disabled

1 = vNet enabled

0 VNMON 1

When vNet is disabled, no vNet expansion modules are used by the system.

Enable installed module positions

Each VNMODUL## parameter represents one fixed vNet position.

Set the parameter only when a supported ADAM module is physically installed in that position. Leave unused positions disabled.

The position and its vNet node address are fixed by the vNet layout. During setup, the user enables the correct predefined position rather than selecting a free node number.

Parameter Index Range Format Default Example
VNMODUL## Fixed position ids 0, 2, 8, 32, 128

0 = Position not used

A supported non-zero value enables the ADAM module assigned to that fixed position

0 VNMODUL30 2

Only the ADAM values used in the standard vNet setup are listed here.

Parameter Disabled Enabled value Enabled result
VNMODUL100 = Position not used2Enables analog input position 1, node 11, ADAM 4017
VNMODUL120 = Position not used8Enables analog input position 2, node 13, ADAM 4017
VNMODUL140 = Position not used32Enables analog input position 3, node 15, ADAM 4017
VNMODUL160 = Position not used128Enables analog input position 4, node 17, ADAM 4017
VNMODUL200 = Position not used2Enables analog output position 1, node 21, ADAM 4024
VNMODUL220 = Position not used8Enables analog output position 2, node 23, ADAM 4024
VNMODUL240 = Position not used32Enables analog output position 3, node 25, ADAM 4024
VNMODUL260 = Position not used128Enables analog output position 4, node 27, ADAM 4024
VNMODUL300 = Position not used2Enables digital input position 1, node 31, ADAM 4051
VNMODUL320 = Position not used8Enables digital input position 2, node 33, ADAM 4051
VNMODUL340 = Position not used32Enables digital input position 3, node 35, ADAM 4051
VNMODUL400 = Position not used2Enables digital output position 1, node 41, ADAM 4056
VNMODUL420 = Position not used8Enables digital output position 2, node 43, ADAM 4056
VNMODUL440 = Position not used32Enables digital output position 3, node 45, ADAM 4056
VNMODUL500 = Position not used2Enables combined digital I/O position 1, node 51, ADAM 4055
VNMODUL520 = Position not used8Enables combined digital I/O position 2, node 53, ADAM 4055
VNMODUL600 = Position not used2Enables relay output position 1, node 61, ADAM 4069
VNMODUL620 = Position not used8Enables relay output position 2, node 63, ADAM 4069

Typical examples

Practical notes