Use this page as a commissioning starting point for supported instruments where the factory or standard communication defaults are known.
Installed equipment can be changed in the field. Always verify the actual address and serial settings before replacing, scanning, or troubleshooting an instrument.
Use this page together with Instruments, Device Model Setup, Network Profiles, and Settings.
Use these public DEVNETPROFILE# values when an instrument default matches the listed communication path. See Network Profiles for the full profile reference.
| Profile | Connection | Baud rate | Serial format | Use when |
1/2 | RS485 Modbus RTU | 9600 | 8N1 | The instrument is a direct RS485 Modbus RTU device using the common 9600 8N1 default. |
3/4 | RS485 Modbus RTU | 38400 | 8N1 | The instrument is a direct RS485 Modbus RTU device configured for 38400 8N1. |
5/6 | RS485 Modbus RTU | 19200 | 8E1 | The instrument is a direct RS485 Modbus RTU device configured for 19200 8E1. |
7/8 | RS485 Modbus RTU | 38400 | 8E1 | The instrument is a direct RS485 Modbus RTU device configured for 38400 8E1. |
9 | Wireless M-Bus | - | - | The meter is read through the wireless M-Bus path. |
10/11 | RS485 OSDP | 38400 | 8N1 | The connected equipment is an OSDP reader or keypad. |
12 | Pulse / digital input | - | - | The instrument exposes a pulse or digital count signal instead of a serial protocol. |
14 | Wired M-Bus | 2400 | - | The meter is a wired M-Bus device at 2400 baud. |
15 | Wired M-Bus | 9600 | - | The meter is a wired M-Bus device at 9600 baud. |
16 | Wired M-Bus | 19200 | - | The meter is a wired M-Bus device at 19200 baud. |
17 | RS232 ASCII serial | 9600 | 8N1 | The instrument uses the technical RS232 serial path. |
18 | TCP/IP | - | - | The instrument is reached through the built-in TCP/IP communication profile. |
19/20 | RS485 | Under review | Under review | Use only when a project standard specifically requires one of these profiles. The serial setting needs confirmation before general commissioning use. |
| Instrument | Setup | Default address | Connection | Baud rate | Serial format | Usable network profiles | Source | Notes |
Thies Hygro-Thermo-Baro Transmitter Compact 1.1006.54.081 |
107109100 Auto or 107109101 specific |
Modbus address 1; range 1..247 |
RS485 Modbus RTU | 9600 | 8N1 | 1 or 2 |
Manufacturer manual and controller support | Use Auto for normal setup. Use the .081 setup only when the installation must be locked to that model. |
| Thies Clima sensors, general Modbus/RS485 family | 107109100 Auto where the controller can identify the sensor |
Sensor-dependent; manufacturer manuals may call this ID, Bus-ID, bus address, or slave address. | RS485 Modbus RTU when configured | Sensor-dependent | Sensor-dependent | Match the configured sensor. | Manufacturer manual, partial, and controller support | Do not copy the Hygro-Thermo-Baro default unless the installed sensor is that Modbus variant. Auto can identify the supported variants listed in Field Instrument Guide. |
| Siemens SITRANS LR110 Modbus | 107116100 Auto or 107116101 specific |
Modbus address 246; range 1..255 |
RS485 Modbus RTU | 9600 | 8N1 | 1 or 2 |
Manufacturer manual and controller support | The manufacturer manual defines the default address, baud rate, parity, and stop bits. |
| Siemens SITRANS LR120 Modbus | 107116100 Auto or 107116102 specific |
Modbus address 246; range 1..255 |
RS485 Modbus RTU | 9600 | 8N1 | 1 or 2 |
Manufacturer manual and controller support | Same Siemens LR1x0 Modbus communication defaults as LR110. |
| OTT CBS Bubble Sensor | 107111100 Auto or 107111101 specific |
Modbus bus address 1; range 1..247 |
RS485 Modbus RTU | 9600 | No parity confirmed; stop bits not confirmed | Not ready for recommendation. | Manufacturer manual, partial, and controller support | Modbus is deactivated by factory default. Confirm the activated Modbus serial format before choosing a network profile. |
| Gill MaxiMet GMX600 | 107110100 Auto or 107110101 specific |
Not confirmed from manufacturer Modbus defaults. Modbus supports networked RS485 use. | RS485 Modbus RTU when configured | 19200 default; 9600 or 19200 for Modbus | Not confirmed | Not ready for recommendation. | Manufacturer manual, partial, and controller support | Exact Modbus address and serial format still need confirmation. Configure the instrument for Modbus before commissioning. |
| Carlo Gavazzi EM530 | See Device Model Setup | Modbus address 1; range 1..247 |
RS485 Modbus RTU | 9600 | 8N1 | 1 or 2 |
Manufacturer manual and controller support | Use the profile for the installed RS485 port. |
| Carlo Gavazzi EM540 | See Device Model Setup | Modbus address 1; range 1..247 |
RS485 Modbus RTU | 9600 | 8N1 | 1 or 2 |
Manufacturer manual and controller support | Use the profile for the installed RS485 port. |
| Janitza Auto | 101112100 |
Not confirmed from manufacturer defaults. | RS485 Modbus RTU | Not confirmed from manufacturer defaults. | Not confirmed | Not ready for recommendation. | Controller support only | Auto is supported by the controller, but the factory address, baud rate, and serial format still need a manufacturer source. |
| Janitza standard | 101112101 |
Not confirmed from manufacturer defaults. | RS485 Modbus RTU | Not confirmed from manufacturer defaults. | Not confirmed | Not ready for recommendation. | Controller support only | The standard Janitza setup is supported by the controller, but the factory address, baud rate, and serial format still need a manufacturer source. |