Use this page when wiring analog transmitters to controller analog inputs. It shows the wiring principles for 4-20 mA and 0-10 V signals before the value is configured for pressure control, alarms, or DataGuard reporting.
Always confirm the transmitter output on the nameplate and in the project diagram before wiring.
Set the controller input to match the transmitter signal before commissioning.
Verify the live analog value before relying on pressure control, alarms, graphs, or logging.
Principle Drawings
The diagrams show how to mount the transmitter in principle. Terminal names vary by controller, so always use the terminal names from the device IO list and the project diagram.
Generic diagram name
Meaning
FlexVander LX9 eco example
Where to confirm
Sensor supply +
Positive supply from the controller when the transmitter is powered by the controller.
DCOUT
Device IO list and project diagram.
Supply 0V
Supply return for the transmitter.
SGND
Device IO list and project diagram.
Analog input
The controller input that reads the 4-20 mA or 0-10 V signal.
AI1 or AI2
Device IO list and parameter setup.
Analog reference
Reference for the analog signal.
AGND
Device IO list and project diagram.
Input Mode Selection
Signal type
Input mode
Check
4-20 mA transmitter
Current input
Install or select current input on the controller. The configured signal type and scaling must match the transmitter range.
0-10 V transmitter
Voltage input
Remove or select voltage input on the controller. Do not use 0-10 V while the input is set for current input.
Diagram Legend
Line
Meaning
Blue
Supply positive.
Grey
Supply return or signal reference.
Green
Analog signal into the controller input.
Dashed grey
Reference or common connection that must follow the project diagram.
Which Diagram Should I Use?
Transmitter nameplate or terminals
Use this diagram
Two terminals and output marked 4-20 mA
4-20 mA two-wire loop
Separate supply terminals and output terminals
4-20 mA powered transmitter
Separate field power supply is used
4-20 mA transmitter with external supply
Output marked 0-10 V
0-10 V voltage transmitter
4-20 mA Two-Wire Loop
A two-wire transmitter uses the same loop for supply and signal. The controller input must be set as a current input.
Transmitter terminal
Controller terminal principle
Use
+
Sensor supply +
Supply positive from the controller when the project uses controller supply.
- / signal
Analog input
Current loop signal into the selected analog input.
Reference if required
Analog reference
Follow the project diagram for any common reference between transmitter supply return and analog reference.
4-20 mA Powered Transmitter
A powered 3-wire or 4-wire transmitter has separate supply terminals and output terminals. The controller input must be set as a current input.
Transmitter terminal
Controller terminal principle
Use
Supply +
Sensor supply + or external supply +
Power the transmitter according to its nameplate.
Supply 0V
Supply 0V or external 0V
Supply return. If the output is not isolated, the analog reference must be common as shown in the project diagram.
OUT+ / Iout
Analog input
Current signal into the selected analog input.
OUT- / reference
Analog reference
Reference for the analog signal.
4-20 mA Transmitter With External Supply
Use an external supply when the transmitter requires another voltage, more current than the controller can supply, or separate field power.
Transmitter terminal
Controller or supply terminal principle
Use
Supply +
External supply +
Positive field supply for the transmitter.
Supply 0V
External supply 0V
Supply return. Connect common reference according to the project diagram unless the output is isolated.
OUT+
Analog input
Current signal into the selected analog input.
OUT- / reference
Analog reference
Reference for the analog signal.
0-10 V Voltage Transmitter
A voltage transmitter sends a voltage signal between the output terminal and the signal reference. The controller input must be set as a voltage input.
Transmitter terminal
Controller terminal principle
Use
Vout / 0-10 V
Analog input
Voltage signal into the selected analog input.
0V / common
Analog reference
Reference for the voltage signal.
Commissioning Checks
Confirm transmitter output type and measurement range before wiring.
Confirm the controller input mode matches the signal type.
Confirm supply voltage and available current for the transmitter.
Confirm signal reference according to the project diagram.
Check the live analog value before enabling automatic control or alarms.
Public revision 21/05/2026
Cookies on Vika Help
Vika Help uses necessary browser storage and, if you allow it, statistics cookies for Google Analytics. You can accept all, reject all, or open settings.
Cookie settings
Choose which categories may be used on Vika Help.
NecessaryAlways on. Required to remember your consent choice and keep the documentation shell working as intended.
Allows Google Analytics to measure aggregate use of the documentation site.