Use this page to configure shared runtime digital outputs, including output function, contact type, operator feedback, and surveillance status output.
Select how the output should work, for example as a pulse output or a normal on/off output.
This determines whether the output changes state momentarily or remains active until it is changed again.
| Parameter | Index | Range | Format | Default | Example |
DWTYPE# |
1..28 | 0..2 |
0 = Pulse output, minimum 500 ms 1 = On/off 2 = On/off, and status is retained after restart |
1 | DWTYPE1 2 |
Select whether the output should behave as NO or NC.
Match the contact type to the connected relay logic, lamp circuit, or external controller input.
| Parameter | Index | Range | Format | Default | Example |
DWCONTACT# |
1..28 | 0..1 |
0 = Normally open (NO) 1 = Normally closed (NC) |
0 | DWCONTACT1 1 |
Use this setting to enable or disable an extra status message after output operation.
When enabled, the operator receives an explicit acknowledgement after manual activation instead of relying only on the physical result.
| Parameter | Index | Range | Format | Default | Example |
DWTXT |
- | 0..1 | 0 = Disabled 1 = Enabled |
0 | DWTXT 1 |
Assign one digital output to show the overall surveillance status.
This is typically used for a status lamp, relay, or external indication point that follows the shared surveillance state.
| Parameter | Index | Range | Format | Default | Example |
SURSTATOUT |
- | 0..digital output number | 0 = Disabled >0 = Digital output number |
0 | SURSTATOUT 1 |