Use this page as the product-specific setup flow for OceanWatcher. Configure the OceanWatcher program settings first, then configure each sensor through the relevant analog input, 1-Wire, DataGuard, or driver communication page.
The system must run the specified ProSoft version or a later version.
Configure the OceanWatcher program state and display name before sensor setup.
OWAFAC loads the factory-defined OceanWatcher defaults.
| Command | Index | Range | Format | Factory | Example |
| OWAFAC | - | - | Loads OceanWatcher factory defaults. | - | OWAFAC |
Enable or disable the OceanWatcher runtime.
| Parameter | Index | Range | Format | Factory | Example |
| OWAPRG | - | 0..1 | 0 = Disabled 1 = Enabled |
0 | OWAPRG 1 |
Set the equipment name used in messages and service displays. If no name is configured, the system name is used.
| Parameter | Index | Range | Format | Factory | Example |
| OWANAME | - | Max 20 characters | Letters or numbers | - | OWANAME Viking |
OceanWatcher can use up to two level sensor channels. Active parser-safe source selection is limited to analog input 1 and analog input 2. Serial radar setup is configured through shared driver communication profiles.
| Parameter | Index | Range | Format | Factory | Example |
| OWAMLEV | - | 0..2 | 0 = Disabled 1 = Analog input 1 2 = Analog input 2 |
0 | OWAMLEV 1 |
For Siemens radar over RS485 Modbus, configure the driver profile on Driver Communication Settings before using the measured value in OceanWatcher or DataGuard. For the current DataGuard water-level flow, set DEVDATATYPE# 9007 on the matching driver profile.
107116101 = Siemens SITRANS LR110107116102 = Siemens SITRANS LR120For a level sensor connected to an analog input, set the analog input scaling before DataGuard reporting. For the current OceanWatcher water-level flow, use VRDATATYPE# 9007.
TMIN# and TMAX# in metres as distance from radar to water. A common LR100 4-20 mA setup is TMIN1 0 and TMAX1 10 for a 0..10 m distance range.9007.| Parameter | Index | Range | Format | Default | Example |
TMIN# |
1..32 | -32768..32767 | Engineering value | 0 | TMIN1 10 |
| Parameter | Index | Range | Format | Default | Example |
TMAX# |
1..32 | -2147483647..2147483647 | Engineering value | 0 | TMAX1 100 |
Recommended level signal damping is VRDMPV# 900 for 90.0% damping.
| Parameter | Index | Range | Format | Default | Example |
VRDMPV# |
1..32 | 0..1000 | Percent of measurement range x 10 | 800 | VRDMPV1 900 |
Recommended damping time is VRDMPT# 1000 ms.
| Parameter | Index | Range | Format | Default | Example |
VRDMPT# |
1..16 | 0..10000 | Milliseconds | 100 | VRDMPT1 80 |
Use the OceanWatcher water-level reference parameters with the same index as the DataGuard 9007 profile. They are station/profile parameters for the OceanWatcher water-level calculation, not analog input scaling values.
| Parameter | Index | Range | Format | Factory | Example |
| OWAWLREF# | 1..2 | -32767..32767 | Radar reference point relative to DVR90 in mm. | - | OWAWLREF1 3200 |
| OWAWLDKLAT# | 1..2 | -32767..32767 | DKLAT/LAT zero relative to DVR90 in mm. If DKLAT is 900 mm below DVR90, use -900. |
- | OWAWLDKLAT1 -900 |
DataGuard 9007 uses these formulas:
DTY 1201 = OWAWLREF# - distance_mm, water level relative to DVR90, signed mm.DTY 1221 = DTY 1201 - OWAWLDKLAT#, water level relative to DKLAT/LAT, signed mm.OWAFORSK# is a legacy OceanWatcher offset used by the older OceanWatcher runtime path. It is not the primary reference parameter for the current DataGuard 9007 water-level flow.
OceanWatcher temperature measurement can be configured through analog inputs, 1-Wire, or delivered driver communication. Configure the source first, then configure DataGuard only when the value must be logged or exported to Emiko.
TMIN# and TMAX# to match the transmitter measurement range.VRDMPV# 999 for 99.9% damping and VRDMPT# 1000 ms.| Parameter | Index | Range | Format | Default | Example |
TMIN# |
1..32 | -32768..32767 | Engineering value | 0 | TMIN1 10 |
| Parameter | Index | Range | Format | Default | Example |
TMAX# |
1..32 | -2147483647..2147483647 | Engineering value | 0 | TMAX1 100 |
| Parameter | Index | Range | Format | Default | Example |
VRDMPV# |
1..32 | 0..1000 | Percent of measurement range x 10 | 800 | VRDMPV1 900 |
| Parameter | Index | Range | Format | Default | Example |
VRDMPT# |
1..16 | 0..10000 | Milliseconds | 100 | VRDMPT1 80 |
For 1-Wire temperature sensors, configure discovery, channel mapping, alarms, and optional DataGuard export on 1-Wire Temperature Setup and Alarms. If the measured value must be exported, continue on DataGuard via 1-Wire.
For FPI Thermalert sensors delivered with OceanWatcher, the emissivity value is normally set to 0.93 for water-surface temperature measurement. See Temperature Sensor Settings for the short product setup note.
Use DataGuard when an OceanWatcher value must be logged or sent to Emiko. For analog sensors, configure the analog input first; for 1-Wire sensors, configure the 1-Wire channel first; for driver values, configure the driver profile first.
VREQT# > 0, VRDATATYPE# > 0, and VRLOGMODE# > 0.VREQT# 20 when the measured value belongs to OceanWatcher.For OceanWatcher water level, 9007 is the current DataGuard selector for both analog radar and supported driver radar. OK/suspect output sends DTY 1220, DTY 1201, DTY 1221, and DTY 1222. Fatal setup, source, range, stale, or warmup states send DTY 1220 only.
| Parameter | Index | Range | Format | Factory | OceanWatcher example |
| VREQT# | 1..32 | 0..35 | Emiko equipment type. Use 20 for OceanWatcher. | 0 | VREQT1 20 |
| VRDATATYPE# | 1..32 | 0..7999, plus supported selectors | Emiko data type or supported selector. Use 9007 for OceanWatcher analog radar water level. |
0 | VRDATATYPE1 9007 |
| VRLOGMODE# | 1..32 | 0..4 | 0 = Disabled, 1 = Periodic, 2 = Change, 3 = Event, 4 = Hybrid. | 1 | VRLOGMODE1 4 |
| VRLOGINT# | 1..32 | 0..31 | Periodic log interval selector. | 19 | VRLOGINT1 19 |
| VRLOGHYS# | 1..32 | 0..32767 | Minimum value change before a new threshold-based value is sent. | 0 | VRLOGHYS1 5 |
For a supported LR110/LR120 driver radar, use the matching driver profile index and set DEVEQT# 20, DEVDATATYPE# 9007, and DEVLOGDATA# 1 on DataGuard via Driver Communication. Use DEVDATATYPE# 1201 only when the driver primary value should be sent directly without the OceanWatcher 9007 package.
For the full shared reference, see DataGuard via analog inputs, DataGuard via 1-Wire, and DataGuard via driver communication.
If a SonTek SL500 current meter is delivered with the installation, configure the current meter model and calibration.
| Parameter | Index | Range | Format | Factory | Example |
| OWAMCUR | - | 0..1 | 0 = Disabled 1 = SonTek SL500 |
0 | OWAMCUR 1 |
| Parameter | Index | Range | Format | Factory | Example |
| OWACALI | - | 0..3600 | Compass calibration in degrees. | 0 | OWACALI 20 |
Direct SonTek write commands are only relevant for systems delivered with SonTek/VD driver support. For command details, see the current meter documentation.
Retired units can be delivered with both internal and external GSM antennas.
Set whether the unit must use an external GSM antenna.
| Parameter | Index | Range | Format | Default | Example |
GSMANT |
1 | 0..1 |
0 = Internal GSM antenna 1 = External GSM antenna connector Note: Internal/external switching is available only on AX9 turbo and AX9 encore. On other supported controllers, runtime keeps external antenna mode. |
- | GSMANT 1 |